Honeywell 1EN2R-9005 0406R3-NE User Manual

Page of 22
EN2R-9005 0406R3-NE
6
L4188 - L6188 SINGLE AQUASTAT - DIRECT IMMERSION 
APPLICATIONS AND ORDERING INFORMATION 
Application
L4188 and L6188 are sensitive, immersion-type water 
temperature thermostats for controlling and limiting boiler 
water temperature in hydronic heating systems.
The thermostat has a liquid-filled sensing element which fits 
into an immersion well (order separately) for direct mounting 
into a boiler, tank or other vessel.
Ordering information
1 = High limit stop
2 = High limit stop at 60°C
3 = Capilliary length 1500 mm and mounting bracket
4 = Without cover and conduit box
5 = Quick connect terminals only
6 = With well assembly
7 = With push-in plug
O.S. number
Application
Temperature 
range 
Switch    
differential (K)
Switch type
Setting means
Remarks   
(see notes)
L4188A 2015
Controller
25 ... 95°C
4
SPST
External knob
-
L4188A 2023
Controller
40 ... 110°C
4
SPST
External knob
5
L4188A 2031
Controller
25 ... 95°C
4
SPST
External knob
5
L4188B 2005
Controller
40 ... 110°C
4
SPST
Internal screw
4 - 5
L4188B 2013
Controller
25 ... 95°C
4
SPST
Internal screw
4 - 5
L6188A 2002
Controller
25 ... 95°C
4 ... 10  
(adjustable)
SPDT
External knob
6
L6188A 2010
Controller
40 ... 110°C
4 ... 10    
(adjustable)
SPDT
External knob
6
L6188A 2028
Controller
25 ... 95°C
4 ... 10    
(adjustable)
SPDT
External knob
3
L6188A 2036
Controller
70 ... 140°C
4 ... 10    
(adjustable)
SPDT
External knob
6
L6188A 2044
Controller
40 ... 110°C
4 ... 10    
(adjustable)
SPDT
External knob
Tradeline   1 - 7
L6188B 2000
Controller
25 ... 95°C
4
SPDT
Internal screw
4
L6188B 2018
Controller
70 ... 140°C
4 ... 10    
(adjustable)
SPDT
Internal screw
3 - 7
L6188B 2026
Controller
40 ... 110°C
4 ... 10    
(adjustable)
SPDT
Internal screw
L6188B 2034
Controller
25 ... 95°C
4 ... 10    
(adjustable)
SPDT
Internal screw
6 - 7
L6188B 2042
Controller
25 ... 95°C
4
SPDT
Internal screw
L6188C 2008
Limiter
70 ... 140°C
Manual reset
SPDT
Internal screw
7
L6188C 2016
Limiter
25 ... 95°C
Manual reset
SPDT
Internal screw
6 - 7