Honeywell 1EN2R-9005 0406R3-NE User Manual
9
EN2R-9005 0406R3-NE
L4189 - L6189 SINGLE AQUASTAT - PANEL MOUNTING (IMMERSION)
SPECIFICATIONS AND DIMENSIONS
Specifications
Ambient temperature limits
0 ... 70°C
0 ... 70°C
Electrical connections
6.3 mm spade terminals
6.3 mm spade terminals
Enclosure
IP40
IP40
Electrical rating
10 A at 250 Vac, resistive load
2,5 A at 250 Vac, inductive load
15 A at 250 Vac, locked motor
250 mA at 30 mVdc (special option)
10 A at 250 Vac, resistive load
2,5 A at 250 Vac, inductive load
15 A at 250 Vac, locked motor
250 mA at 30 mVdc (special option)
Terminal data
C-1 breaks on temperature rise (SPDT and SPST)
C-2 makes on temperature rise (SPDT only)
C-1 breaks on temperature rise (SPDT and SPST)
C-2 makes on temperature rise (SPDT only)
Capilliary length
350 mm, 1000 mm, 1500 mm and 2000 mm
350 mm, 1000 mm, 1500 mm and 2000 mm
Accessories
Immersion wells, see page 18
Immersion wells, see page 18
Fig. 3. Internal schematics L4189/L6189
Fig. 4. Dimensional drawing L4189/L6189
+
C
+
1
C
SPDT
SPST
1
2
Panel
C
1
2
Mounting hole (2) for M4x20
tread forming screw
tread forming screw
Hole ( 4 min.) in
panel for tool reset
panel for tool reset
47.1
5
48
48
48
60
14
14.4
32
32
16
18
17
85
30.5
28.5
2 mm max