White Rodgers 50A65-843 User Manual
2
SPECIFICATIONS
ELECTRICAL RATINGS [@ 77°F (25°C)]:
Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp
Max. Input Current @ 25 VAC: 0.45 amp
Relay Load Ratings:
Valve Relay:
1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay:
2.0 amp @ 120 VAC 50/60 Hz
(resistive)
(resistive)
Flame Current Requirements:
Minimum current to insure flame detection: 1 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:
-40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
5% to 93% relative humidity (non-condensing)
MOUNTING:
Surface mount multipoise
Timing Specs: (@ 60 Hz**)
maximum
Flame Establishing Time:
0.8 sec
Flame Failure Response Time:
2.0 sec
** At 50 Hz, all timing specifications should be increased by
20%
Gases Approved: Natural, Manufactured, Mixed, Liquified
Petroleum, and LP Gas Air Mixtures are all approved for use.
Petroleum, and LP Gas Air Mixtures are all approved for use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise)
PRE-PURGE
IGNITOR WARM-UP
IGNITION ACTIVATION
PERIOD
PERIOD
TRIAL FOR IGNITION
PERIOD
PERIOD
RETRIES
VALVE SEQUENCE PERIOD
INTERPURGE
POST-PURGE
LOCKOUT TIME
HEAT DELAY-TO-FAN-ON*
HEAT DELAY-TO-FAN-OFF*
COOL DELAY-TO-FAN-ON
COOL DELAY-TO-FAN-OFF*
AUTO RESET
HUMIDIFIER
ELECTRONIC AIR CLEANER
30
20
1
4
2 times
12
60
15
300
30, 45
60/90/
120/180
5
45, 90
60 minutes
YES
YES
50A65-843
* These times will vary depending on
option switch position. The control is
factory-set at 30 seconds heat delay-
to-fan-on, 180 seconds heat delay-to-
fan-off and 45 seconds cool delay-to-
fan-off. See OPERATION section for
further information.
factory-set at 30 seconds heat delay-
to-fan-on, 180 seconds heat delay-to-
fan-off and 45 seconds cool delay-to-
fan-off. See OPERATION section for
further information.