American Water Heater BCG3 User Manual

Page of 52
13
HOT WATER
OUTLET
TO TANK
INLET
CHECK
VALVE
MIXING
VALVE
COLD
WATER
INLET
TEMPERED WATER
OUTLET
12” TO 15”
(30-38 cm)
CHECK
VALVE
figure 10.
dishwashing maChines
All dishwashing machines meeting the national Sanitation 
Foundation requirements are designed to operate with water 
flow pressures between 15 and 25 pounds per square inch 
(103 kPa and 173 kPa). Flow pressures above 25 pounds 
per square inch (173 kPa), or below 15 pounds per square 
inch  (103  kPa),  will  result  in  improperly  sanitized  dishes. 
Where  pressures  are  high,  a  water  pressure  reducing  or 
flow regulating control valve should be used in the 180°F 
(82°C)  line  to  the  dishwashing  machine  and  should  be 
adjusted to deliver water pressure between these limits.
The  national  Sanitation  Foundation  also  recommends 
circulation of 180°F (82°C) water. The circulation should be just 
enough to provide 180°F (82°C) water at the point of take-off to 
the dishwashing machine.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 
circulating line on the outlet side of the pump. never throttle flow 
on the suction side of a pump. See Water Piping Diagrams in 
this manual.
Closed water systems
Water  supply  systems  may,  because  of  code  requirements 
or such conditions as high line pressure, among others, have 
installed  devices  such  as  pressure  reducing  valves,  check 
valves, and back flow preventers. Devices such as these cause 
the water system to be a closed system.
thermal expansion
As water is heated, it expands (thermal expansion). In a closed 
system the volume of water will grow when it is heated. As the 
volume of water grows there will be a corresponding increase in 
water pressure due to thermal expansion. Thermal expansion 
can cause premature tank failure (leakage). This type of failure 
is not covered under the limited warranty. Thermal expansion 
can also cause intermittent Temperature-Pressure relief Valve 
operation:  water  discharged  from  the  valve  due  to  excessive 
pressure  build  up.  This  condition  is  not  covered  under  the 
limited warranty. The Temperature-Pressure relief Valve is not 
intended for the constant relief of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 
all  closed  systems  to  control  the  harmful  effects  of  thermal 
expansion. Contact a local plumbing service agency to have a 
thermal expansion tank installed.
See Water line Connections on page 20 and the Water Piping 
Diagrams beginning on page 35.
temperature-pressure relief ValVe
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and 
certified combination Temperature-Pressure relief Valve (T&P 
valve) by the manufacturer. The valve is certified by a nationally 
recognized testing laboratory that maintains periodic inspection 
of production of listed equipment of materials as meeting the 
requirements for relief Valves for hot Water Supply Systems, 
AnSI Z21.22 • CSA 4.4, and the code requirements of ASMe.
If replaced, the new T&P valve must meet the requirements 
of local codes, but not less than a combination Temperature-
Pressure relief Valve rated/sized and certified as indicated in 
the above paragraph. The new valve must be marked with a 
maximum set pressure not to exceed the marked hydrostatic 
working pressure of the water heater (150 psi = 1,035 kPa) 
and a discharge capacity not less than the water heater Btu/
hr  or  kW  input  rate  as  shown  on  the  water  heater’s  model 
rating label.
nOTe: In addition to the factory installed Temperature-Pressure 
relief  Valve  on  the  water  heater,  each  remote  storage  tank 
that may be installed and piped to a water heating appliance 
must  also  have  its  own  properly  sized,  rated  and  approved 
Temperature-Pressure relief Valve installed. Call the toll free 
technical  support  phone  number  listed  on  the  back  cover  of 
this manual for technical assistance in sizing a Temperature-
Pressure relief Valve for remote storage tanks.
For  safe  operation  of  the  water  heater,  the  Temperature-
Pressure relief Valve must not be removed from its designated 
opening nor plugged. The Temperature-Pressure relief Valve 
must  be  installed  directly  into  the  fitting  of  the  water  heater 
designed for the relief valve. Install discharge piping so that 
any  discharge  will  exit  the  pipe  within  6  inches  (15.2  cm) 
above an adequate floor drain, or external to the building. In 
cold  climates  it  is  recommended  that  it  be  terminated  at  an 
adequate drain inside the building. Be certain that no contact is 
made with any live electrical part. The discharge opening must 
not be blocked or reduced in size under any circumstances. 
excessive length, over 30 feet (9.14 m), or use of more than 
four  elbows  can  cause  restriction  and  reduce  the  discharge 
capacity of the valve.