American Water Heater VG6250T76NV Series 100 User Manual

Page of 40
35
trouBleshootInG GuIdelInes
trouBle shootInG
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.
Read the GENERAL SAFETY INFORMATION section first.
INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL
#
led status
proBleM
solutIon
1
The gas control valve/thermostat 
has sensed inadequate or no earth 
ground.
1  Ensure the wall outlet (power supply) is properly
grounded.
2  Ensure all ground connections/wires on the water 
heater are securely connected.
2
The gas control valve/thermostat 
has sensed reversed polarity in the 
120 VAC power supply.
1  Ensure the wall outlet/power supply is properly wired.
2  Ensure all internal 120 VAC wiring connections and 
wiring harness have no reversed wires. 120 VAC "hot" 
wire must connect to the on/off switch.
3
Pressure switch circuit remaining 
closed for more than 5 seconds 
after heating cycle begins.
Blower may not start in this 
condition.
1  Ensure air pressure switch circuit wiring is correct and 
the air pressure switch is not jumpered.
2  Replace the air pressure switch.
4
Pressure switch circuit remains 
open longer than 5 seconds after 
the blower is energized.
Blower may run continuously in 
this condition.
1  Ensure the air pressure switch sensing tube is properly 
connected at both ends and is not kinked or damaged.
2  Ensure the correct size of vent and intake air pipe (direct
vent products) was used per the installation instructions
in the manual that came with the water heater.
3  Ensure maximum number of elbows or maximum 
equivalent feet of vent or intake air pipe has not been 
exceeded per the installation instructions in the manual 
that came with the water heater.
4  Ensure there are no obstructions in the vent or intake air pipe.
5
The gas control valve/thermostat 
has detected an open igniter circuit.
1  Check wiring to the hot surface igniter assembly - 
replace igniter assembly if wiring is damaged or worn.
2  Check resistance of the igniter at igniter assembly 
plug - should be between 11 and 18 ohms at room 
temperature (77° F at plug end) - replace igniter if open
or shorted.
3  Check igniter assembly plug and the socket on the gas 
control valve/thermostat for good connection.
4  Replace igniter assembly if the plug is worn or damaged.
5  Replace the gas control valve/thermostat if the igniter 
assembly socket on the bottom of the control is worn or 
damaged.
6
Ignition/flame failure.
The gas control valve/thermostat 
has reached the maximum number 
of retries (3) for ignition and is
currently locked out for one hour.
Cycle the power to the water heater 
off and on to reset.
1  Ensure flame sensor is making good contact with the
burner flame and ensure flame is steady. Also ensure
supply and manifold gas pressures are within the 
requirements in the installation manual.  
2  Gas supply is turned off - pressure is too low. 
3  Ensure the flame sensor is clean - use fine steel wool
to clean the flame sensor.
4  Check igniter assembly plug and the socket on the 
bottom of the gas control valve/thermostat for good 
connection. Replace igniter assembly if the plug is worn 
or damaged.  Replace the gas control valve/thermostat if 
socket is worn or damaged.
5  Replace igniter assembly.