Rosemount 2230
5-10
Section 5. Service and Troubleshooting
5.3.2
Device Warnings
Device warnings are signaled in the Input Register Device Warnings. 
Warnings are less serious than errors. Detailed information about the different 
warning types can be found in Input registers 1050 - 1070.
Table 5-5.  Device warnings 
Configuration Error
Input register no. 1124.
Bit 1: Unit Not Supported
Choose a supported measurement unit
numHiddenErrors
Input register no. 1132.
Number of hidden errors.
Contact Emerson Process 
Management/Rosemount TankGauging 
service department.
numOtherErrors
Input register no. 1134.
Number of other errors.
(1) The register number refers to the internal Input Register of the 2230 database. 
Note that Input Register data from the 2230 display is temporarily stored in the Input Register database of the 2410 Tank Hub. The Input 
Registers presented in TankMaster WinSetup refer to the internal register area of the 2410. Therefore, for tank 1 you will have to add 16000 
to the 2230 internal register number as given by Table 5-4
 in order to find the register presented by WinSetup. For the second and third 
2230 display you will have to add 18000 and 20000, respectively.
Message
Description
Action
Message
Description
Action
RAM warning
Input register no. 1050
(1)
.
The application software could not be 
started.
Bit 0: Stack low
Contact Emerson Process 
Management/Rosemount TankGauging 
service department.
FPROM warning
Input register no. 1052
Not used
Hreg warning
Input register no. 1054.
Bit 0: Default Holding register values 
used
Contact Emerson Process 
Management/Rosemount TankGauging 
service department.
Other memory warning
Input register no. 1056
Not used
Display warning
Input register no. 1058
Not used
Modem warning
Input register no. 1060
Not used
Other hardware warning
Input register no. 1062
Not used
Measurement warning
Input register no. 1064
Not used
ITEMP warning
Input register no. 1066.
Bit 0: The internal temperature is out 
of range
Contact Emerson Process 
Management/Rosemount TankGauging 
service department.
Software warning
Input register no. 1068.
Bit 1: Stack low (less then 10% left of 
stack)
Bit 2: Software startup
Configuration warning
Input register no. 1070
Bit 11: Invalid Model Code String
Bit 12: Invalid Model Code 
(1) The register number refers to the internal Input Register of the 2230 database. The Input Registers presented in TankMaster WinSetup 
refer to the internal register area of the 2410. For tank 1 add 16000 to the 2230 internal register number as given by Table 5-5 in order to 
find the register presented by WinSetup. For the second and third 2230 display you will have to add 18000 and 20000, respectively.