Runco CW-95DHD User Manual
CineWall™ Installer/Integrator Manual
15
PRE
L
IMINAR
Y
3.1
Site Requirements
Site Requirements
Prior to installing the CineWall, confirm that the installation site meets the requirements
described in this section.
described in this section.
Infrastructure
The CineWall is designed for installation into a dedicated, framed, structurally capable wall
with at least 32.50 inches (826 mm) of distance between the user-viewable surface of this
wall and anything immediately behind the open framed area. The chassis protrudes
approximately 30.75 inches (781 mm) from the front of the dedicated wall into the cavity.
with at least 32.50 inches (826 mm) of distance between the user-viewable surface of this
wall and anything immediately behind the open framed area. The chassis protrudes
approximately 30.75 inches (781 mm) from the front of the dedicated wall into the cavity.
3. Installation Preparation
32.50” minimum
30.75”
AC Outlet
48
” M
AXIM
UM