1.7.6   Mounting requirements and hints
Temperature compensation
When hot water (max. 75°C) is used in the system due regard should be paid to thermal expan-
sion of the pipes when mounting the system. When raising the temperature from10°C to 75°C 
the system will expand some 0.7 mm/m. In order to allow for this expansion long straight lines 
should be fitted with compensators in the form of U-bends or hose connections. The pipe system 
should not be fixed too close to any corners and close to Tee connectors at outlet points.
U-bends/hose connections
At a max. temperature on the system of 75°C a compensator should be fitted at 20 m intervals 
if there are no elbows on the line. If the pipe may expand at one end compensators may be left 
out if the pipe is not fixed at the Tee connectors at the same time. Compensation for ∅15 and 
∅22 should be in the form of hose connections or as U-bends on the pipe. Use hose connec-
tions for ∅30.
COMPENSATION
 
Pipe 
Hose no. 
Hose no. stainless  L (mm)    L min (mm)    R min (mm)
  ∅15 
6300453 
6301191 
350 
450 
40
  ∅22 
6300453/6300454* 
6301191/6202161*  350/480 
550 
55
  ∅30 
6300454 
6202161 
480
* If the pipe line carries more than the water volume from 3 pumps 6300454 respectively 6202161 
hoses should be fitted.