Mitsubishi Electronics MR-J2S- CL User Manual

Page of 337
3 -  25
3. SIGNALS AND WIRING
3.7.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to Section 12.1.
Symbol
Connection Target
(Application)
Description
Supply L
1
, L
2
 and L
3
 with the following power:
For 1-phase 230VAC, connect the power supply to L
1
/L
2
 and leave L
3
 open.
Servo amplifier
Power supply
MR-J2S-10CL
to 70CL
MR-J2S-100CL
to 700CL
MR-J2S-10CL1
to 40CL1
3-phase 200 to 230VAC,
50/60Hz
L
1
L
2
L
3
1-phase 230VAC,
50/60Hz
L
1
L
2
1-phase 100 to 120VAC,
50/60Hz
L
1
L
2
L
1
, L
2
, L
3
Main circuit power supply
U, V, W
Servo motor output
Connect to the servo motor power supply terminals (U, V, W).
Servo amplifier
Power supply
MR-J2S-10CL to 700CL
MR-J2S-10CL1 to
40CL1
1-phase 200 to 230VAC,
50/60Hz
L
11
L
21
1-phase 100 to 120VAC,
50/60Hz
L
11
L
21
L
11
, L
21
Control circuit power supply
P, C, D
Regenerative brake option
1) MR-J2S-350CL or less
Wiring is factory-connected across P-D (servo amplifier built-in regenerative
brake resistor).
When using the regenerative brake option, always remove the wiring from
across P-D and connect the regenerative brake option across P-C.
2) MR-J2S-500CL or more
Wiring is factory-connected across P-C (servo amplifier built-in regenerative
brake resistor).
When using the regenerative brake option, always remove the wiring from
across P-C and connect the regenerative brake option across P-C.
Refer to Section 14.1.1 for details.
N
Return converter
Brake unit
When using the return converter or brake unit, connect it across P-N.
Do not connect it to the servo amplifier of MR-J2S-350CL or less.
Refer to Sections 14.1.2 and 14.1.3 for details.
Protective earth (PE)
Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.