15. COMMUNICATION FUNCTIONS 
 
15.9 Initialization 
After the slave station is switched on, it cannot reply to communication until the internal initialization 
processing terminates. Hence, at power-on, ordinary communication should be started after. 
(1) 1s or more time has elapsed after the slave station is switched on; and 
(2) Making sure that normal communication can be made by reading the parameter or other data which 
does not pose any safety problems. 
 
15.10 Communication procedure example 
The following example reads the set value of parameter No.2 "function selection 1" from the servo 
amplifier of station 0. 
Data item 
Value 
Description 
Station number 
Servo amplifier station 0 
Command 05 
Read command 
Data No. 
02 
Parameter No.2 
 
Checksum  30H  30H  35H  02H  30H  32H  03H   FCH
0 2
STX
ETX
5
0
Yes
No
Yes
No
No
No
Yes
Yes
Yes
No
[0][0][5]            [0][2]
[0]
Axis No. Command
Data No.
Data
Start
Data make-up
Checksum calculation and
addition
Addition of SOH to make
up transmission data
Data transmission
Data receive
Is there receive data?
3 consecutive times?
Error processing
Other than error code
[A]   [a]?
Receive data analysis
End
300ms elapsed?
3 consecutive times?
Error processing
100ms after EOT transmission
STX
ETX
SOH
Transmission data
Master station     slave station
Master station     slave station
Master station     slave station
46H 43H
F C
5
0
STX
0 2 ETX
0