Trane BCVC User Manual

Page of 92
BCXC-SVX01B-EN
41
Installation Piping
Steam Piping
Proper installation, piping and trapping is necessary to insure satisfactory heating coil operation 
and prevent operational damage under service conditions. These installation recommendations 
and piping diagram (see 
) must be followed to assure satisfactory, trouble-free 
operation.
General
1.
Support all piping independently of coils.
2. Provide swing joints or flexible fittings in all piping connections adjacent to heating coils to 
absorb expansion and contraction strains.
3. Install coils so air passes through fins in proper direction (stenciled on top of coil channel).
Steam Coils
NOTICE
Coil Condensate!
Condensate must flow freely from the coil at all times to prevent coil damage from water 
hammer, unequal thermal stresses, freeze-up and/or corrosion. In all steam coil installations, the 
condensate return connections must be at the low point of the coil. Failure to follow these 
instructions could result in equipment damage. 
1.
Install 1/2-inch 15-degree swing check vacuum breaker in unused condensate return tapping as 
close as possible to coil. Vent vacuum breaker line to atmosphere or connect into return main 
at discharge side of steam trap. Vacuum relief is particularly important when coil is controlled 
by modulating steam supply or two-position (on-off) automatic steam supply valve.
2. Proper steam trap selection and installation is necessary for satisfactory coil performance and 
service life.
a. Select trap based on maximum possible condensate rate and recommended load factors.
b. Locate steam trap discharge at least 12 inches below condensate return tapping. This 
provides sufficient hydrostatic head pressure to overcome trap losses and assure complete 
condensate removal.
c. Float and thermostatic traps are preferred because of gravity drain and continuous 
discharge operation.
d. Use float and thermostatic traps with atmospheric pressure gravity condensate return with 
automatic controls or where possibility of low pressure supply steam exists.
e. Bucket traps should only be used when supply steam is unmodulated and 25 psig or higher.
f. When installed with series airflow, size traps for each coil using capacity of first coil in airflow 
direction.
g. Always trap each coil separately to prevent condensate holdup in one or more coils.
h. Always install strainers as close as possible to inlet side of trap.
3. Use V-port modulating valves to obtain gradual modulating action or slow opening 2-position 
valves to prevent steam hammer.
Note: Contact the factory for recommendations regarding steam coil valve selections 
compatible with Tracer™ ZN controllers.
4. Use normally-open non-modulating control valves if coils are exposed to freezing air.
Note: Contact the factory for recommendations regarding steam coil valve selections 
compatible with Tracer™ ZN controllers.
5. Control each coil bank separately when installing coils for series airflow with automatic steam 
control valves.