Diagnostics
 
Diagnostics
Translating Multiple Diagnostics
The controller senses and records each diagnostic independently of other diagnostics. It is possible 
to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they 
occur.
Possible diagnostics include:
Table 39. Tracer ZN010 and ZN510 test sequence for 1-heat/1-cool configurations
Steps
Fan
Cool output
(a)
(a) At the beginning of step 2, the controller attempts to clear all diagnostics.
Heat output
Damper
J1-1, J1-3
 J1-
J1-
J1-
1. Off
Off
Off
Off
Closed
2. Fan high
High
Off
Off
Closed
3. Exhaust fan
(b)
(b) Tracer™ ZN010 and ZN510 have a binary output default as “none” on J1-X from the factory. If the unit has a 2-speed fan, 
step 3 will energize the low fan speed. If the unit has a single speed fan, step 3 will continue to energize the high fan speed. 
This binary output can be reconfigured as an exhaust fan, with the use of Rover™ software.
Off
Off
Closed
4. Fan
Low
Off
Off
Closed
5. Cool
High
On
Off
Closed
6. Heat
High
Off
On
Closed
7. Two-position damper
(c)
(c) After the fresh air damper step, the test sequence performs the exit step.This initiates a reset and attempts to return the 
controller to normal operation.
High
Off
Off
Open
8. Exit
(d)
(d) For all 1-heat/1-cool applications including 2-pipe changeover, the cooling and heat test stage energize. This occurs even 
though during normal 2-pipe changeover operation binary output controls the unit valve for both cooling and heating.
Note: The 2-position damper energizes during this step if the controller is configured for a 2-position damper.
Table 40. Tracer ZN520 test sequence
Step
Fan
Main 
valve
Electric heat or 
aux. valve
Fresh air 
damper
Generic/baseboard heat
J1-1
J1-2
J1-3
J1-5
J1-6
J1-9
J1-10
J1-11
J1-12
TB4-1
1. Off
(a)
Off
Off
Off
Off
On
EH: off
Off
aux: on
Off
On
Off
2. Fan high
(b)
High
Off
Off
Off
Off
Off
Off
Off
Off
Off
3.
(c)
Off
Off
Off
Off
Off
Off
Off
Off
Off
4. Fan low
Off
Off
Low
Off
Off
Off
Off
Off
Off
Off
5. Main open
High
Off
Off
On
Off
Off
Off
Off
Off
Off
6. Main close, EH1 on
High
Off
Off
Off
On
On
Off
Off
Off
Off
7. Aux. open
High
EH1 on
Exh
(d)
Off
Off
Off
On
Off
Off
Off
Off
8. Aux. close, damper open
High
Off
Off
Off
Off
Off
EH1 off
On
EH2 on
On
Off
Off
9. Damper close
High
Off
Off
Off
Off
Off
Off
Off
On
Off
10. Generic/baseboard heat energized High
Off
Off
Off
Off
Off
Off
Off
Off
On
11. Exit
(e)
Exit
(a) Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives.
(b) At the beginning of step 2, the controller attempts to clear all diagnostics.
(c) The low fan speed output energizes at step 3. If the unit is configured for a 1 speed fan, the fan remains on high speed at step 3.
(d) If the unit is configured for a 1- or 2-speed fan, and BOP2 is configured for an exhaust fan, the exhaust fan output energizes on step 7. The exhaust 
fan output is shared with medium speed.
(e) After step 10, the test sequence performs an exit. This initiates a reset and attempts to return the controller to normal operation.