Black Box MPSH16-D20-120V User Manual

Page of 193
CHAPTER 7:  Alarm Configuration
 
101
7.  Alarm Configuration
When properly configured, the Outlet Managed PDU can meter current, temperature 
and voltage readings, and log this information for future review.  In addition, the 
Outlet Managed PDU can also generate alarms when current or temperature readings 
exceed user-defined trigger levels, when input voltage is lost or restored to the unit, 
when a circuit breaker is open (may not apply to all models,) when a Ping-No-
Answer condition is detected, when the Invalid Access Lockout feature is triggered 
or when current consumption for a Plug or Plug Group rises too high or falls too low.
When any of these conditions are detected, the Outlet Managed PDU can send an 
"Alarm" to the proper personnel via Email, Syslog Message or SNMP trap.  If the 
user-defined trigger levels for temperature and current load are exceeded, the Outlet 
Managed PDU can also automatically shut off power to non-essential devices (Load 
Shedding) in order to decrease current load and/or the amount of heat generated 
within the rack.  After Load Shedding has taken place, the Outlet Managed PDU can 
then restore power to the non-essential devices when temperature and/or current load 
drop to user-defined acceptable levels.
This section describes the procedure for setting up the Outlet Managed PDU to send 
alarm messages when any of these critical situations are detected.  For instructions 
regarding configuration of the Log function, please refer to Section 5.3.3.
Notes:
•  In order to send alarm notification via email, email addresses and 
parameters must first be defined as described in Section 5.9.11.  
Email alarm notification will then be sent for all alarms that are 
enabled as described in this Section.
•  In order to send alarm notification via Syslog Message, a Syslog 
address must first be defined as described in Section 5.9.2.  Once 
the Syslog address has been defined, Syslog Messages will be 
sent for every alarm that is discussed in this Section, providing 
that the Trigger Enable parameter for the alarm is set to "On."
•  In order to send alarm notification via SNMP Trap, SNMP Trap 
parameters must first be defined as described in Section 5.9.7.  
Once SNMP Trap Parameters have been defined, SNMP Traps will 
be sent for every alarm that is discussed in this Section, providing 
that the Trigger Enable parameter for the alarm is set to "On."
•  When defining parameters via the Text Interface, make certain 
to press the [Esc] key to completely exit from the configuration 
menu and save newly defined parameters.  When parameters are 
defined via the Text Interface, newly defined parameters will not 
be saved until the "Saving Configuration" message is displayed.