CHAPTER 4:  Installation
 
25
4.  Hardware Installation
4.1. 
Connecting the Power Supply Cables
4.1.1.  Installing the Power Supply Cable Keepers
The Outlet Managed PDU includes cable keepers, which are designed to prevent the 
power supply cables from being accidentally disconnected from the unit.
•  MPSH8-S20-120V, MPSH8-S20-120V, MPSH8-D20-120V and 
MPSH8-D20-208+V Models:  The cable keepers for these units must be 
installed by the user.  
1.  First make certain that both of the Outlet Managed PDU’s two power 
cables are disconnected from the power source.
2.  Install the two standoff screws (included with the cable keeper) in the 
two vacant screw holes, located between the two power inlets.  When 
the standoff screws are in place, thread the two screws supplied with the 
cable keeper into the top end of both of the standoff screws.
3.  Connect the power cables to the power inlets.  Check to make sure that 
both cables are firmly seated in the power inlet connectors.
4.  Install the cable keeper plate, by slipping the plate over the two screws 
which protrude from the top of the standoffs.  Slip the cable keeper 
plate into place, so that the notches in the bottom of the plate slip over 
the power cables, and the holes in the middle of the plate align with the 
screws in the tops of the standoffs.  
5.  Tighten the two screws into the standoffs to secure the plate and the 
power supply cables to the unit.  Check to make certain that the cables 
are held firmly in place by the cable keepers.
•  MPSH16-D20-120V and MPSH16-D20-208+V Models:  These units 
include pre-installed cable keepers.  When attaching the power supply cables 
to the unit, first swing the cable keepers out of the way, then plug the power 
cables securely into the power inputs.  When the cables are in place, snap the 
cable keepers over each plug to secure the cables to the unit.