Roberts Gorden 100 User Manual

Page of 60
SECTION 7: V
ENTING
13 of 47
Vents and air intakes must be adequately 
supported so that the heater does not bear the 
weight of the pipes.
For vent termination 
See Page 14, Figure 8 through 
Page 18, Figure 13.
7.3.1 Standard Vented Heaters 
         (Models UHD[X] 75 - 125)
The vent must be fitted with a low resistance 
terminal. 
See Page 14, Figure 8 through Page 16, 
Figure 10. Standard vented heaters do not allow 
outdoor air intake for combustion air.
7.3.2 Separated Combustion Heaters 
         (Models UHD[X]S 75 - 125)
The heaters are designed to be installed as 
separated combustion heaters. The vent and air 
intake are run as separate pipes to the wall or roof 
terminals. 
See Page 17, Figure 11. As an option, the 
vent and air intake are run as separate pipes to a 
concentric vent box and a concentric vent/air intake 
pipe penetrates the wall or roof. 
See Page 17, Figure 
12 and Page 18, Figure 13.
For separated combustion installation, the vent and 
air intake must be fitted with an individual and 
correctly sized sealed system and the vent and air 
intake must terminate at approved wall and roof 
terminals.
Separated combustion units may not be common 
vented. 
See Page 12, Section 7.
7.4 Unvented Operation
This heater is not approved to be installed in 
residential buildings.
For unvented operation in commercial installations, 
sufficient building ventilation must be provided in the 
amount of 4 cfm per 1000 Btu/h firing rate (United 
States); 3 cfm per 1000 Btu/h firing rate (Canada).
7.5 Horizontal Venting
Horizontally vented heaters must be individually 
vented.
Vent pipe must be sloped ¼" (.6 cm) downward for 
every 1' (.3 m). For vent lengths greater than 5' (1.5 
m), condensation will form. Insulation is 
recommended and condensation drains may be 
desired.
In noncombustible walls only, vent terminal 
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or 
noncombustible walls, use vent terminal (P/N 
90502100) or equivalent insulated vent terminal. 
Follow the manufacturer's instructions for proper 
installation.
Instead of an insulated vent terminal, a listed thimble 
with 2" (5 cm) air gap may be used with a 4" (10 cm) 
vent cap (P/N 90502102).
7.6 Vertical Venting
Vertically-vented standard-vented heaters can be 
common vented (up to four heaters). 
For vent lengths greater than 5' (1.5 m), 
condensation will form. Insulation is recommended 
and condensation drains may be desired. Venting 
through the top of the heater cabinet is not 
recommended if vent lengths are longer than 
10' (3 m). In this case, vent from the rear of the 
heater cabinet then run the vent vertically and use a 
condensate drain at the bottom of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every 
1' (.3 m).
For 4'' (10 cm), an approved vent cap
(P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap 
(P/N 90502103) must be used.
For common vertical venting of more than two 
heaters, 
See Page 16, Figure 10.
A vent shall not extend less than 2' (.6 m) above the 
highest point where it passes through a flat roof of a 
building. 
7.7 Length Requirements
If using vent lengths greater than 5' (1.5 m), 
condensation will form in the vent pipe. Insulation 
and additional sealing measures (high temperature 
silicone at all seams) are required. 
The entire vent should be insulated with foil faced 
fiberglass insulation (1/2" thick, 1-1/2# density 
minimum).
WARNING
Carbon Monoxide Hazard
Heaters may be installed 
vented or unvented.
Vented heaters must be 
vented outdoors.
Unvented heaters must be 
installed according to the 
installation manual.
Failure to follow these 
instructions can result in 
death or injury.