14.4 Troubleshooting for Gas Valves
14.5 Troubleshooting for Flue Blower 
Valve faulty.
Replace with one of 
correct type.
Fault elsewhere.
Correct pressure problem.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Valve Operating
TROUBLESHOOT ENDS.
No
Yes
Valve or ignition control
faulty. Replace with 
one of correct type.
Does gas pressure at
outlet of valve return to zero or 
lower when valve turns off?
No
Yes
Does gas pressure at outlet
of the valve rise when 
valve turns on?
No
Yes
Is gas pressure at inlet of the 
valve correct for gas type?
Note pressure found.
No
Yes
START
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Blower Operating
TROUBLESHOOT ENDS.
No
Blower motor faulty.
Replace with correct type.
Check blower motor leads 
for loose connections.
Correct power
supply problem.
Yes
START
Does 
blower 
turn on and
off while burner is firing 
continuously?
No
Yes
Does flue blower run
automatically when there
is a call for heat?
No 
Yes
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon 
LLC.
Conduct start-up procedure as shown 
on Page 26, Section 11.