Generac 5982R User Manual

Page of 20
6
2.2  CORD SETS AND CONNECTION PLUGS
2.2.1  120 VAC DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 14 Amp circuit 
breaker (Figure 7). 14 Amps of current may be drawn from each socket, 
however, total power drawn must be kept within data plate ratings. Use 
only high quality, well insulated, 3-wire grounded cord sets rated for 125 
Volts at 20 Amps (or greater).
2.2.2  120/240 VAC, 20A TWISTLOCK RECEPTACLE
This is a 120/240 Volt outlet protected against overload by a 14 
Amp circuit breaker (Figure 7). Connect a suitable 4-wire grounded 
cord set to the plug and to the desired load. The cord set should 
be rated for 250 volts at 20 amps (or greater) if the 120/240 
receptacle is used along with 120 volt receptacle. The total load 
drawn must not exceed the data label ratings.
IMPORTANT: Do not overload the generator. Also, do not overload 
individual panel receptacles. These outlets are protected against 
overload with circuit breakers. If amperage rating of any circuit 
breaker is exceeded, that breaker opens and electrical output 
to that receptacle is lost. Read “Don’t Overload the Generator” 
carefully.
Figure 7 - 120 VAC Duplex & 120/240 VAC Twistlock
2.3  HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the 
generator helpline at 1-888-436-3722.
n
  Never operate in an enclosed area or 
indoors! NEVER use in the home, or in 
partly enclosed areas such as garages, 
even if doors and windows are open! ONLY 
use outdoors and far from open windows, 
doors, vents, and in an area that will not 
accumulate deadly exhaust.
n
 The engine exhaust fumes contain carbon 
monoxide, which can you cannot see or 
smell. This poisonous gas, if breathed 
in sufficient concentrations, can cause 
unconsciousness or even death.
n
 Adequate, unobstructed flow of cooling and 
ventilating air is critical to correct generator 
operation. Do not alter the installation or 
permit even partial blockage of ventilation 
provisions, as this can seriously affect safe 
operation of the generator. The generator 
MUST be operated outdoors.
n
 This exhaust system must be properly 
maintained. Do nothing that might render the 
exhaust system unsafe or in noncompliance 
with any local codes and/or standards.
n
 Always use a battery operated carbon 
monoxide alarm indoors, installed according 
to the manufacturers instructions.
2.3.1  GROUNDING THE GENERATOR
The National Electrical Code requires that the frame and 
external electrically conductive parts of this generator be 
properly connected to an approved earth ground (Figure 8)

Local electrical codes may also require proper grounding of the 
unit. For that purpose, connecting a No. 10 AWG (American Wire 
Gauge) stranded copper wire to the grounding lug and to an 
earth-driven copper or brass grounding rod (electrode) provides 
adequate protection against electrical shock. However, local codes 
may vary widely. Consult with a local electrician for grounding 
requirements in the area.
Proper grounding of the generator will help prevent electrical 
shock
 in the event of a ground fault condition in the generator 
or in connected electrical devices. Proper grounding also helps 
dissipate static electricity, which often builds up in ungrounded 
devices.
Figure 8 - Grounding the Generator
Operation