Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, 
ISO3046 and DIN6271).  * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.  Maximum power 
decreases about 3.5 percent for each 1,000 feet above sea level.  Sound output ratings from certain points on the generator subject to change based on installation parameters.
GENERATOR
Model 005875-1 (20 kW)
Rated Maximum Continuous Power Capacity (LP)
20,000 Watts* 
Rated Maximum Continuous Power Capacity (NG) 
18,000 Watts*
Rated Voltage
240 
Rated Maximum Continuous Load Current – 240 Volts
83.3 LP/75 NG
Total Harmonic Distortion
Less than 5%
Main Line Circuit Breaker
90 Amp
Phase
1  
Number of Rotor Poles
Rated AC Frequency
60Hz
Power Factor
1
Battery Requirement (not included) 
Group 26R 12 Volts and 525 Cold-cranking Amperes Minimum
Unit Weight (Pounds/Kilos)
451/204.6
Dimensions (L x W x H) Inches/mm
48 x 25 x 29 (1218 x 638 x 732)
Sound output in dB(A) at 23 ft.  with generator operating at normal load
66
Sound output in dB(A) at 23 ft. with generator in Quiet-Test™ low speed exercise mode 
60
ENGINE
Model 005875-1 (20 kW)
Type of Engine
GENERAC OHVI V-TWIN
Number of Cylinders
2
Displacement
999cc
Cylinder Block
Aluminum w/Cast Iron Sleeve
Valve Arrangement
Overhead Valve
Ignition System
Solid-state w/Magneto
Governor System
Electronic
Compression Ratio
9.5:1
Starter
12 Vdc
Oil Capacity Including Filter
Approx. 1.9 Qts./1.8L
Operating RPM
3,600
Fuel Consumption
Natural Gas 
 
cu.ft./hr.
 
1/2 Load
 
Full Load
Liquid Propane
 
ft3/hr (gal/hr) [Liter/hr]
 
1/2 Load
 
Full Load
206
294
69 (1.89) [7.15]
106 (2.90) [10.98]
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
CONTROLS
2-Line Plain Text LCD Display
Simple user interface for ease of operation.
Mode Switch
-Auto 
Automatic Start on Utility failure. 7 day exerciser.
-Off
Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start)
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds
Standard
Engine Start Sequence
Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).
Engine Warm-up
5 seconds
Engine Cool-Down
1 minute
Starter Lock-out
Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection
Standard
Automatic Low Oil Pressure Shutdown
Standard
Overspeed Shutdown
Standard, 72Hz
High Temperature Shutdown
Standard
Overcrank Protection
Standard
Safety Fused
Standard
Failure to Transfer Protection
Standard
Low Battery Protection
Standard
50 Event Run Log
Standard
Future Set Capable Exerciser
Standard
Incorrect Wiring Protection
Standard
Internal Fault Protection
Standard
Common External Fault Capability
Standard
SPECIFICATIONS