9
1.10  BATTERY INSTALLATION
Fill  the  battery  with  the  proper  electrolyte  fluid  if 
necessary  and  have  the  battery  fully  charged  before 
installing it.
Before installing and connecting the battery, complete 
the following steps:
1.  Set the generator's AUTO/OFF/MANUAL switch to 
OFF.
2.  Turn  off  utility  power  supply  to  the  transfer 
switch.
3.  Remove the 5 amp fuse from the generator con-
trol panel.
  If the AUTO/OFF/MANUAL switch is not set to its 
OFF position, the generator can crank and start 
as soon as the battery cables are connected. If 
the utility power supply is not turned off, spark-
ing can occur at the battery posts and cause an 
explosion.
Battery cables were factory connected at the genera-
tor  (Figure  1.5).  Connect  cables  to  battery  posts  as 
follows:
4.  Connect the red battery cable (from starter con-
tactor) to the battery post indicated by a positive, 
POS or (+).
5.  Connect  the  black  battery  cable  (from  frame 
ground) to the battery post indicated by a nega-
tive, NEG or (—).
6.  Replace the 5 amp fuse in the generator control 
panel.
NOTE:
Damage will result if battery connections are made 
in reverse.
Figure 1.5 – Battery Cable Connections
NOTE:
The  generator  is  equipped  with  a  battery  trickle 
charger that is active when the unit is set up for 
automatic  operation.  With  the  battery  installed 
and  utility  power  source  voltage  available  to  the 
transfer  switch,  the  battery  receives  a  trickle 
charge while the engine is not running, to prevent 
self-discharge.  The  trickle  charger  is  designed  to 
help  extend  the  life  of  the  battery  by  maintain-
ing the battery when the unit is not running. The 
trickle charge feature cannot be used to recharge 
a discharged battery.
1.11  THE BATTERY
Servicing of the battery is to be performed or super-
vised  by  personnel  knowledgeable  of  batteries  and 
the required precautions. Keep unauthorized person-
nel away from batteries.
When replacing the battery, use the following type of 
battery:  Group  26/26R  12-volt  battery  with  a  rating 
of 350 cold-cranking amps minimum for 7 kW; 525 
cold-cranking amps minimum for 12 and 15 kW at
-18º C (0º F) minimum. When using a maintenance-
free battery, it is not necessary to check the specific 
gravity  or  electrolyte  level.  Have  these  procedures 
performed  at  the  intervals  specified  in  the  “Service 
Schedule.” A negative ground system is used. Battery 
connections are shown on the wiring diagrams. Make 
sure the battery is correctly connected and terminals 
are  tight.  Observe  battery  polarity  when  connecting 
the battery to the generator set.
DANGER
  Do not dispose of the battery in a fire. The 
battery is capable of exploding.
  A battery presents a risk of electrical shock 
and high short circuit current. The following pre-
cautions are to be observed when working on 
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
•  Do not lay tools or metal parts on top of the 
battery; and
•  Disconnect charging source prior to connecting or 
disconnecting battery terminals.
  Do not open or mutilate the battery. Released 
electrolyte has been known to be harmful to the 
skin and eyes, and to be toxic.
  The electrolyte is a dilute sulfuric acid that is 
harmful to the skin and eyes. It is electrically 
conductive and corrosive. 
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators