Page of 4
 
STANDBY 
PRIME
 
                                      SD100 
 
                                      SD100 
GENERATOR OUTPUT VOLTAGE/KW-60Hz 
 
Rated AMP 
 
Rated AMP
  120/240V, 1-phase, 1.0 pf 
100 
417 
91 
379
  120/208V, 3-phase, 0.8 pf 
100 
347 
91 
316
  120/240V, 3-phase, 0.8 pf 
100 
301 
91 
274
  277/480V, 3-phase, 0.8 pf 
100 
150 
91 
137
  600V, 3-phase, 0.8 pf 
100 
120 
91 
109
MOTOR STARTING KVA
  Maximum at 35% instantaneous voltage dip 
208/240/416V 
480V 
208/240/416V 
480V
    with standard alternator; 60 Hz 
206 
275 
206 
275
FUEL
  
Fuel consumption—60 Hz 
Load
 
25% 
50% 
75% 
100% 
25% 
50% 
75% 
100%
   
gal./hr. 
2.3 
4.3 
5.9 
7.7 
1.9 
3.5 
5.1 
6.3
   
liters/hr. 
8.7 
16.2 
22.4 
29.0 
7.1 
13.3 
19.4 
23.9
  Fuel consumption—50 Hz 
gal./hr. 
1.8 
3.4 
4.7 
6.1 
1.5 
2.8 
4.1 
5.0
   
liters/hr. 
7.0 
12.9 
17.9 
23.2 
5.7 
10.6 
15.5 
19.1
  Fuel pump lift 
 
 
36" 
 
 
36"
COOLING
  Coolant capacity 
System - US gal. (lit.) 
5.5 (20.8) 
5.5 (20.8)
   
Engine - US gal. (lit.) 
3.75 (14.2) 
3.75 (14.2)
  Coolant flow/min. 
60 Hz - US gal. 
38 
38
  Heat rejection to coolant 60 Hz full load  BTU/hr. 
280,000 
252,000
  Inlet air* 
60 Hz - cfm (m
3
/min.) 
7500 (212.4) 
7500 (212.4)
 Max. air temperature to radiator*
° C (°F)
60 (140)
60 (140)
 Max. operating ambient temperature*  °C (°F)
50 (122)
50 (122)
COMBUSTION AIR REQUIREMENTS
  Flow at rated power 
60 Hz - cfm (m
3
/min.) 
351 (10.0) 
320 (9.1) 
EXHAUST
  Exhaust flow at rated output  60 Hz - cfm (m
3
/min.) 
988 (28.0) 
880 (24.9)
  Max recommended back pressure 
 Inches Hg
 
1.5 
1.5
 Exhaust temperature 60 Hz (full load)  °F (°C)
1050 (566)
990 (532)
  Exhaust outlet size 
 
4.0" O.D. 
4.0" O.D.
ENGINE
  Rated RPM 
60 Hz  
1800 / 1500 
1800 
  HP at rated KW 
60 Hz  
158 / 122 
144 / 99
  Piston speed 
60 Hz - ft./min. (m/min.) 
1500 (457) 
1500 (457)
  BMEP 
60 Hz / psi 
248  
225
 
DERATION FACTORS
  Temperature 
   
-4.1% for every 10
o
C above - °C
40
40
   
-2.3% for every 10
o
F above - °F
104
104
  Altitude
   
-0.8% for every 100 m above - m 
1067 
1067
   
-2.5% for every 1000 ft. above - ft. 
3500 
3500
OPERATING DATA
NOTE:  Consult your 
Generac dealer for 
additional voltages.
SD100
* Note:  Values given are maximum temperatures to which power adjustments can be applied.  Consult your Generac
 
Power Systems representative if operating conditions exceed these maximums.