page 34 — DCa40sskU/kU4i 60 hz generaTor • operaTion anD parTs manUal — rev. #1 (03/11/13) 
GeneratOr sHut-dOWn prOCedures
2.  Place the engine speed control switch (Figure 51) in 
the Start/Idle position (down).
Figure 51. Engine Speed Control Switch 
Start Idle Position
3.  Let the engine cool by running it at low speed for 3-5 
minutes with no load applied.
4.  Place  the  ignition  switch  (Figure  52)  in  the “
sTop” 
position, remove the key and store in a safe place.
Figure 52. Ignition Switch (Stop Position)
5.  Remove all loads from the generator.
6.  Inspect entire generator for any damage or loosening of 
components that may have occurred during operation.
emergenCY shUTDoWn proCeDUre
1.  Turn ignition switch key to the
 sTop position.
2.  To shut-down the engine in the event of an emergency, 
switch the 
main, gFCi and loaD (Figure 50) circuit 
breakers to 
oFF position.
aUTomaTiC shUT-DoWn sYsTem
This unit is equipped with safety devices to automatically 
stop the engine in the event of low oil pressure, approximately 
7 psi (49 kPa), or high water temperature, approximately 
230° F (110° C). The alarm lamps on the Engine Control 
Panel illuminate to signify the reason for the shutdown.
START/IDLE
NOTICE
Before inspecting, turn the ignition switch to the 
sTop 
position, place all circuit breakers in the
 oFF position 
and allow sufficient time for adequate cooling.  When 
ready to restart, complete all steps in the Generator 
Startup Procedure section of this manual.
10.  Place the 
main, gFCi, and aux. circuit breakers in the 
on position (Figure 48).
Figure 48. Main, Aux. and GFCI  
Circuit Breakers (ON)
11.  Observe  the  generator’s  ammeter  (Figure  49)  and 
verify it reads the anticipated amount of current with 
respect to the load. The ammeter will only display a 
current reading if a load is in use.
Figure 49. Ammeter (Load)
12.  The generator will run until manually stopped or an 
abnormal condition occurs.
normal shUTDoWn proCeDUre
To shutdown the generator, use the following procedure:
1.  Place both the 
main, gFCi and loaD circuit breakers 
as shown in Figure 50 to the 
oFF position..
Figure 50. Main, GFCI and Load 
Circuit Breakers Off
  Warning
never  stop  the  engine  suddenly  except  in  an 
emergency.