MITSUBISHI MGS SERIES 
DIESEL GENERATOR SET 
MGS0500B 
 
 
 
Type & Design 
MGS standard 7310 programmable microprocessor control-automatic start/stop panel, generator breaker control, 
indicating the operational status and fault conditions; automatically shutting down the engine and indicating the engine 
failure by means of LCD display and LEDs on the front panel. 
 
Controls & Monitoring 
◆  Mode selection & start engine button with interlock key switch system 
◆  Menu navigation button 
◆  LCD display for: AC amperage-each phase and earth current, AC voltage-each phase and neutral, Frequency Hz, 
Operation hours run, Lub.    Oil pressure, Cooling water temperature, Generator Load kW/kVA/kVar, Generator Load 
kWh/kVAh/kVarh 
◆  Operation status LED indicators 
◆  CB control buttons 
◆  Mute/Lamp test button 
◆  Voltage adjuster 
◆  Speed adjuster 
◆  Emergency stop pushbutton 
◆  Provided 5 outputs for status as standard equipment (Programmable 8 outputs available as option) 
 
Safety Shutdown Protection and LED Indicators 
High engine temperature, Low oil pressure, Fail to start, Generator Over Speed/Frequency, 
Generator Under Speed/Frequency 
Generator High Voltage, Generator Low Voltage, Oil pressure sender circuit, Loss of Speed signal , Emergency stop, 
 
Mounting 
Fabricated cubicle mounted on individual bracket with anti-vibration isolator 
 
Electrical Design 
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive.   The optional 
interface can provide real time diagnostic facilities. 
 
Generator Control Panel Description 
■  3 position operation mode control key switch 
(ACTIVE, PANEL LOCK, STOP/RESET) 
■  Manual button 
■  Stop/Reset button (Manual only) 
■  Auto button 
■  Mute/Lamp test button (Manual only) 
■  CB open button (Manual only) 
■  Voltage adjusting trimmer 
■  CB close button (Manual only) 
■  Speed adjusting trimmer 
■  Start engine button (Manual only) 
■  Emergency stop pushbutton 
 
■  LCD display accessed by scroll pushbutton 
Generator volts L1-N, L2-N, L3-N 
Engine cooling water temperature (°C & °F) 
Generator volts L1-L2, L2-L3, L3-L1 
Battery volts 
Generator amps L1, L2, L3 
Engine hours run 
Generator Earth Current 
Generator Load kW, kVA, kVar 
Generator Frequency Hz 
Generator Load kWh, kVAh, kVarh 
Engine speed RPM 
Power Factor 
Engine oil pressure (PSI & Bar) 
Generator Phase Sequence 
 
■  Visual indicators on LCD display 
Shutdown alarm 
Generator high current 
Warning alarm 
Over voltage (AC) 
High coolant temperature 
Under voltage (AC) 
Low oil pressure 
Over voltage (DC) 
Charge fail 
Under voltage (DC) 
Over-speed 
Auxiliary indication 
Under-speed 
Auxiliary alarm (warning or shutdown) 
Electrical trip 
Common alarm 
Fail to stop 
Over frequency 
 
Under frequency 
 
■  Visual indication alarm and automatically shutdown 
High engine temperature 
Over frequency 
Low oil pressure 
Under frequency 
Fail to start 
Oil pressure sender open circuit 
Over-speed 
Loss of speed signal 
High voltage 
High Crankcase internal pressure (MGS-C Continuous only) 
Low voltage 
Emergency Stop 
 
■  Operation status indicated by LED 
Remote start present 
Lubrication oil filter clogged 
Generator ready 
Electrical trip 
 
■  Pre-Programmed Starting Unit 
Automatic start/stop sequence timing and delay systems configured 
via MS-Windows based software. 
MGS SERIES 7310 GENERATOR CONTROL PANEL