Generac Power Systems 5255 User Manual

Page of 72
  
17
Section 3 — Operation
Air-cooled Generators
4.  Use the manual transfer handle inside the trans-
fer switch to move the main contacts to their 
STANDBY position, i.e., loads connected to the 
standby power source (Figure 3.2).
5.  To crank and start the engine, set the AUTO/OFF/
MANUAL switch to MANUAL.
6.  Let the engine stabilize and warm up for a few 
minutes.
7.  Set the generator’s main circuit breaker to its ON 
(or CLOSED) position. The standby power source 
now powers the loads.
Figure 3.2 – Manual Transfer Switch Operation
 3.4.2  
TRANSFER BACK TO UTILITY POWER 
SOURCE
When utility power has been restored, transfer back 
to that source and shut down the generator. This can 
be accomplished as follows:
1.  Set the generator’s main circuit breaker to its 
OFF (or OPEN) position.
2.  Let the engine run for a minute or two at no-load 
to stabilize the internal temperatures.
3.  Set the generator’s AUTO/OFF/MANUAL switch to 
its OFF (or OPEN) position. The engine should 
shut down.
4.  Check that utility power supply to the transfer 
switch is turned OFF.
DANGER
  Do not attempt to activate the transfer switch 
manually until all power voltage supplies 
to the switch have been positively turned off. 
Failure to turn off all power voltage supplies 
may result in extremely hazardous and possibly 
fatal electrical shock.
‹
5.  Use the manual transfer handle inside the trans-
fer switch to move the main contacts back to their 
UTILITY position, i.e., loads connected to the util-
ity power source (Figure 3.2).
6.  Turn ON the utility power supply to the transfer 
switch using the means provided.
7.  Set the system to automatic operation as outlined 
in Automatic Transfer Operation section.
3.5  SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. 
Once it is set, the generator will start and exercise 
once every seven days, on the day of the week and at 
the time of day the following sequence is completed. 
During this exercise period, the unit runs for approx-
imately 12 minutes and then shuts down. Transfer of 
loads to the generator output does not occur during 
the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 3.1) per-
mits selection of the day and time for the system to 
exercise. At the chosen time, perform the following 
sequence to select the desired day and time of day 
the system will exercise. Remember seasonal time 
changes affect the exercise time settings.
1.  Verify that the AUTO/OFF/MANUAL switch is set 
to AUTO.
2.  Press and hold the "Set Exercise Time" switch for 
several seconds, then release. All the red LED's 
will flash for approximately 10 seconds and then 
stop.
3.  Once the red LED's stop flashing, the generator 
will start and run for approximately 12 minutes 
and then shut down. The exerciser is now set to 
run at this time of day each week.
 
Example:  If the "Set Exercise Time" switch is 
pressed on Saturday afternoon at 2:00 p.m., the 
generator will start and exercise for approximate-
ly 12 minutes every Saturday at 2:00 p.m..
NOTE:
The exerciser will only work in the AUTO mode 
and will not work unless this procedure is per-
formed. The exerciser will need to be reset every 
time the 12-volt battery is disconnected and then 
reconnected, and when the 15A fuse is removed.
The 16kW unit has a low speed exercise option. Dip 
switch 1 on the control board is factory set to OFF. 
This allows the engine to run at a slower speed dur-
ing weekly exercise periods for quieter operation. If 
this Dip switch is set to ON, the generator will exer-
cise at it's normal speed.
This DIP switch position is only read at board power 
up. If the DIP switch position is changed, power to 
the board must be cycled for the micro controller to 
recognize the new DIP switch position.