Section 6
TROUBLESHOOTING FLOWCHARTS
The  “Flow  Charts”  in  this  section  may  be  used  in 
conjunction  with  the “Diagnostic Tests”  of  Section  7. 
Numbered  tests  in  the  Flow  Charts  correspond  to 
identically numbered tests of Section 7.
Problems 1 through 4 apply to the AC generator only.
Beginning with Problem 5, the engine DC control sys-
tem is dealt with.
Page 25
If Problem Involves AC Output
VOLTAGE & 
FREQUENCY BOTH 
HIGH OR LOW
FREQUENCY GOOD – 
VOLTAGE HIGH
OR
VOLTAGE LOW
FREQUENCY GOOD – 
ZERO OR RESIDUAL 
VOLTAGE 
NO-LOAD VOLTAGE 
& FREQUENCY 
GOOD
TEST 1 – CHECK 
NO-LOAD VOLTAGE 
& FREQUENCY
GO TO PROBLEM 1
GO TO VOLTAGE 
REGULATOR ADUST-
MENT, PAGE xx
GO TO PROBLEM 2
GO TO PROBLEM 4
INTROdUCTION
Problem 1 – Voltage & Frequency Are Both High or Low
FREQUENCY GOOD. 
LOW OR RESIDUAL 
AC VOLTAGE
NO-LOAD FREQUENCY & 
VOLTAGE GOOD BUT THEY 
DROOP TO MUCH WHEN 
LOAD IS APPLIED
FREQUENCY IS GOOD BUT 
NO-LOAD VOLTAGE IS 
HIGH OR VOLTAGE IS LOW
TEST 2 – CHECK 
STEPPER MOTOR 
CONTROL
GO TO 
PROBLEM 2
GO TO 
PROBLEM 4
GO TO VOLTAGE 
REGULATOR 
ADJUSTMENT, 
PAGE 9