Section 7
DIAGNOSTIC TESTS
 4.  If no movement is seen in Step 3 remove the con-
trol  panel  cover. Verify  the  six  pin  connector  (j2) 
on  the  Printed  Circuit  Board  is  seated  properly, 
remove the connector and then replace it and test 
again. Verify the dip switches are correctly set.
NOTE: The  dip  switches  on  the  Printed  Circuit 
Board are factory set in the “OFF” or dOWN posi-
tion. Refer to Figure 5.2 on Page 22.
5.  If  problem  continues  remove  six  pin  connector 
(j2) from Printed Circuit Board. Set Volt meter to 
measure  ohms.  Carefully  measure  from  the  end 
of the six pin harness as follows:
RED
EMPTY
YELLOW
BROWN
ORANGE
BLACK
Figure 7-2. Six Pin J2 Connector Wire Colors
NOTE:  Press  down  with  the  meter  leads  on  the 
connectors  exposed  terminals,  do  not  probe  into 
the connector.
a. Connect  one  meter  lead  to  Red,  connect  the 
remaining test lead to Orange, approximately 10 
ohms should be measured.
b. Connect  one  meter  lead  to  Red,  connect  the 
remaining  test  lead  to Yellow,  approximately  10 
ohms should be measured.
c. Connect  one  meter  lead  to  Red,  connect  the 
remaining test lead to Brown, approximately 10 
ohms should be measured.
d. Connect  one  meter  lead  to  Red,  connect  the 
remaining  test  lead  to  Black,  approximately  10 
ohms should be measured.
e. Connect  one  meter  lead  to  Red,  connect  the 
remaining  test  to  the  stepper  motor  case.  No 
resistance  should  be  measured  (“Infinity”  or 
Open).
RESULTS:
1.  If  the  stepper  motor  fails  any  part  of  Step  5 
replace the stepper motor.
2.  If the stepper motor passes all steps replace the 
Printed Circuit Board.
TEST 4 – FIxEd ExCITATION TEST/ROTOR 
AMP dRAW
DISCUSSION:
The  fixed  excitation  test  consists  of  applying  bat-
tery  voltage  (12 VDC)  to  the  Rotor  windings. This 
allows  that  portion  of  the  excitation  circuit  between 
the Voltage  Regulator  and  the  Rotor  (including  the 
Rotor itself) to be checked as a possible cause of the 
problem. When battery voltage is applied to the Rotor, 
the  resulting  magnetic  field  around  the  Rotor  should 
induce a Stator power winding voltage equal to about 
one-half the unit’s rated output voltage.
6
0
4
13 13
2
4
22S
11S
15
JUMPER WIRE
WIRES 4 REMOVED FROM
VOLTAGE REGULATOR
VOLTAGE
REGULATOR
FUSE HOLDER (F1) 
RED TEST LEAD
BLACK TEST LEAD
Figure 7-3. – Fixed Excitation Test, Step A
PROCEDURE:
1.  Disconnect  Wire  4  from  the Voltage  Regulator 
(VR). (Third terminal from the right side of VR).
2.  Connect a jumper wire to Wire 4 and to the 12 volt 
fused  battery  positive  supply Wire  15,  located  at 
the fuse (F1) holder (see Figure 7-3).
NOTE: during this test, Wire 15 must remain con-
nected to the fuse (F1) holder.
3.  Set the VOM to measure AC voltage.
Page 37