Pelco KBD300A User Manual

Page of 40
Pelco Manual C527M-L (3/04)         
13 ]
Connecting KBD300A Remote Keyboards
For remote keyboard connections, use COM 5, 6, 7, or 8 for the CM6800-48X8 and COM 4 and 5 for the
CM6800-32X6. Each port can support up to eight KBD300A keyboards. Do not exceed 16 total keyboards
for the CM6800-48X8 and eight total keyboards for the CM6800-32X6.
A KBDKIT or KBDKIT(-X) is required to connect remote keyboards. Each kit contains two RJ-45 wall blocks
and a transformer. Use one wall block for each keyboard.
Refer to Figure 4 (CM6800-48X8 shown).
Pick a suitable location for each keyboard and wall block. Wall blocks must be within 6 feet (1.8 m) of
a suitable electric outlet. Do not mount the wall blocks yet.
Connect each keyboard to a wall block, using the supplied keyboard data cable.
Remove the wall block covers and wire the connections between each wall block. Connect to a final
wall block (which will be connected to the CM6800).
Communication to the keyboards is RS-485. Maximum cable distance for RS-485 communication over
24-gauge wire is 4,000 feet (1,219 m). Pelco recommends using shielded twisted pair cable that
meets or exceeds the basic requirements for EIA RS-485 applications.
At each wall block, wire the KBDKIT or KBDKIT(-X) transformer to pins 3 and 4.
Replace the wall block cover. Secure the wall block to a suitable surface using the double-sided
sticky pad.
Set the address switches for each keyboard (refer to the 
Switch Settings 
section). (If using COM 7 or
8, the port settings on the CM6800 must be changed from the default settings. Refer to the CM6800
manual.)
Connect the final wall block to COM 5, 6, 7, or 8 on the CM6800-48X8 or COM 4 or 5 for the CM6800-
32X6 using a straight data cable (supplied with the CM6800).
Plug the KBDKIT or KBDKIT-X transformers into a suitable outlet.
To initialize the keyboard, wait five seconds after powering-up the CM6800, enter the number for the
monitor you are viewing, and press MON. The LED display shows the number entered.
NOTE:  You must re-initialize whenever power is cycled.
��
Go to the 
Programming and Operation 
section and program and test for proper operation.