Siemens 9350 User Manual

Page of 176
9300 Series User’s Guide
Using the Modbus/TCP Protocol
Chapter 3 - Default Meter Functionality 
Page 59
You can use the Modbus RTU protocol to write values into ION external numeric, 
pulse and Boolean modules, allowing you to enable, disable and reset meter 
functions. You can also use Modbus to change setup register values in various ION 
modules to configure the meter’s operation.
All of the information required to write to ION registers through Modbus is 
available in 9300 & 9330 Modicon Modbus Protocol, available on the Technical 
Documentation CD, or by request from Siemens.
Using the Modbus/TCP Protocol
Modbus/TCP is the newest open Modbus protocol variant (formerly called 
MBAP). It defines the packet structure and connection port (port 502) for the 
industry standard TCP/IP protocol. The structure of Modbus/TCP is very similar 
to the Modbus RTU packet except that it has an extra six-byte header and does not 
use the cyclic redundancy check (CRC). Some of the newest ION firmware now 
supports Modbus/TCP for direct communications with the meter. 
Modbus/TCP retains the Modbus RTU limit of 256 bytes to a packet. It is suggested 
that higher through-put is possible if this limitation is removed. This variant is 
called Enhanced Modbus/TCP but, so far, few devices have moved to support it.
Another variant, that has yet to gain popularity, is from the Semiconductor 
Equipment and Materials International (SEMI) trade association. The Generic 
Sensor-Bus Sub-Committee created the Sensor/Actuator Network Standard (SEMI 
E54-0997). 
Modbus TCP Communications
You can now communicate to the meter via Modicon
®
 Modbus TCP (formerly 
called MBAP). Your meter must have the optional Ethernet port.
Connect to socket 502.
Be aware that you cannot form an EtherGate connection to the Modbus TCP 
network.
Ethernet
Connect to socket 502
Meter with optional
Ethernet port