ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it would
be called Direct Acting. If a negative error should cause the output to increase
(i.e. heating), it would be called Reverse Acting.
Press  
d
18) Display flashes 
DRçT Direct or RVRS Reverse.
Press  
b
19) Scroll through the available selections: “Direct” or “Reverse”.
Press  
d
20) Display shows 
STRD stored message momentarily and then
advances to 
AUTo  only, if it was changed, otherwise press a to
advance to 
AUTo  Auto PID Submenu (if PID Control Type was
selected).
If “ON/OFF” was selected in the Control Type, the display skips
to the Dead Band Submenu.
AUTO PID SUBMENU:
Press  
d
21) Display flashes 
ENBL or DSBL.
Press  
b
22) Scroll through the available selections: “Enable” or
“Disable”.
Press  
d
23) Display shows 
STRD stored message momentarily and then
advances to 
ANTL only, if it was changed, otherwise press a to
advance to 
ANTL Anti Integral Submenu.
If “Enabled”, the controller can determine, by enabling Start PID, the
optimum values for the three adjustments — Proportional, Reset and
Rate corresponding to P, I, and D. These values may be changed once
the auto tuning is complete. 
If “Disabled” is selected, the user will manually enter these three
adjustment values. If you want the instrument to do the auto PID and the
P , PI or PID, first select auto disable and enter 0000 for unwanted
parameter. i.e. for PI enter 0000 for the rate.
ANTI INTEGRAL SUBMENU:
Press  
d
24) Display flashes 
ENBL or DSBL.
Press  
b
25) Scroll through the available selections: “Enable” or “Disable”.
Press  
d
26) Display shows 
STRD stored message momentarily and then
advances to 
STRT only, if it was changed, otherwise press a to
advance to 
STRT to Start Auto Tune PID Submenu (If auto PID
was Enabled).
If Auto PID was disabled display advances to 
PRoP
Proportional Band Submenu.