Module E11 
Status: 01/2010                                                                     Radio Frequency Identification (RFID) with SIMATIC S7-300F-2PN/DP and 
RF180C 
 
5.6 
Programming a Restart or Warm Restart 
 
A restart of the MOBYIM (interface module) is carried out by setting the variable "init_run".  
With "init_run“, the IM and FB45 are re-parameterized and synchronized. 
 
"init_run“ is necessary after the following: 
 
• Switching on the SIMATIC (OB 100) 
• Switching on the power supply for the IM 
• PROFINET communication is interrupted 
• An error indication by the variable "error_BUS" 
• A transponder type change; for example from RF300 to ISO or vice versa 
• Changing an INPUT parameter in DB45 (Reader_Parameter) 
 
 
Generating OB100  
 
 
 
 
 
Open OB100 and enter the program 
 
 
 
 
Save and close OB100