PowerLogic ION7550 / ION7650 Installation Guide
14 
© 2007 Schneider Electric.  All rights reserved.
3-Wire Solid-Grounded Wye, 3-Element, Direct Connection
 
When the common or star point of a 3-wire Wye system is grounded, 
the meter may be connected directly without using PTs, provided that the 
phase voltages are within the meter’s range.
VOLTS MODE = 4W-Wye
3-Wire Delta, 2½-Element, Direct Connection 
600 V L-L max.
VOLTS MODE = Delta
3-Wire Delta, 2-Element 2 PTs & 2 CTs
 
Use PTs for voltages over 600 V L-L.
VOLTS MODE = Delta
LINE
LOAD
Fuse for N/- terminal 
required if its supply 
source is ungrounded 
Connect G terminal
to ground for AC 
power source