Schneider Electric ION7550 User Manual

Page of 28
PowerLogic ION7550 / ION7650 Installation Guide
22 
© 2007 Schneider Electric.  All rights reserved.
NETWOR
K SETUP
IP ADDRESS
Sets the IP address for the meter
000.000.000.000 to 
999.999.999.999
varies
3
SUBNET MASK
Used if subnetting applies to your 
network
000.000.000.000 to 
999.999.999.999
255.240.0.0
GATEWAY
Used in multiple network 
configurations
000.000.000.000 to 
999.999.999.999
0.0.0.0
DNS PRIMARY
Sets the address for the primary 
DNS Server that is configured to 
resolve domain names
000.000.000.000 to 
999.999.999.999
none
DNS 
SECONDARY
Sets the address for the secondary 
DNS Server that is configured to 
resolve domain names
000.000.000.000 to 
999.999.999.999
none
10/100BT 
CONFIG
Sets the BASE-T Ethernet max. link 
speed and duplexing
Auto, 10BT half, 10BT full, 
100BTX half, 100BTX full
Auto
100BFX CONFIG Sets the Fiber Ethernet duplexing
Full Duplex or Half Duplex
Full Duplex
SNMP SERVER
Determines whether SNMP protocol 
is enabled on the meter or not
Enabled or Disabled
Disabled
PQ
 SETUP
SWELL LIMIT
Specifies the magnitude above 
which an input must rise for a swell 
to be recorded
100 to 1000
106
SAG LIMIT
Specifies the magnitude below 
which an input must fall for a sag to 
be recorded
0 to 100
88
CHANGE 
CRITERIA
Specifies the amount by which an 
input must change during a 
disturbance to be considered a new 
sub-disturbance
0 to 100
10
NOMINAL 
VOLTAGE
4
Specifies the nominal voltage of the 
power system
0 to 1,000,000
0
EVENT PRIORITY Assigns a priority level to sag/swell 
events
0 to 255
200
FO
RMA
T SE
TU
P
DIGIT GROUP
Specifies symbols used to delimit 
thousands & decimal place holder
1000.0 or 1,000.0 or 1000,0
1000.0
VOLTS DECIMAL Number of decimal places 
displayed for voltages
1. to 123456789.XXX
1.XX
CURRNT 
DECIMAL
Number of decimal places 
displayed for currents
1. to 123456789.XXX
1.XXX
POWER DECIMAL Number of decimal places 
displayed for power measurements 1. to 123456789.XXX
1.XXX
MEAS SYMBOL
Specifies the convention used for 
displaying measurements
IEEE or IEC
IEEE
PHASE LABEL
Specifies how phases are labelled
ABC, RST, XYZ, RYB, RWB, 123
ABC
PF SIGN
Specifies the power factor sign 
convention used
IEEE or IEC
IEEE
PF SYMBOL
Sets how power factor is labelled
(LD = leading/LG = lagging)
LD/LG, +/-, CAP/IND
LD/LG
DATE FORMAT
Specifies how dates are displayed
MM/DD/YYYY, DD/MM/YYYY, 
YYYY/MM/DD
MM/DD/
YYYY
TIME FORMAT
Specifies whether time is displayed 
in 12 hour or 24 hour clock format 12 H or 24 H
24 H
DISPLAY DST
Specifies whether or not DST is 
displayed
Yes or No
Yes
Menu
Setting
Description
Range (Values)
Default