Delay Relay Output Board Option 
Hydrastep 2468CB and 2468CD Manual 
3b-16 
24685034
 
3b.3.2.7  ‘Two out of Three’ Relay Alarm System 
In the following diagrams (7A & 7B) 

 indicate the electrode channel selected for each 
relay.  A fully functioning system (NO FAULTS) will cause a low level trip at electrode level 2.  
Using high-level electrode channels and SW5 set to ES, the circuit can perform a high level trip. 
Note: Inputs from electrodes 1 & 2 are applied to two separate relays on their respective boards. 
Case A - Relays normally energised, de-energise two to trip 
(Relays shown in de-energised state) 
1
4
3
2
5
8
7
6
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
1
4
3
2
5
8
7
6
To alarm
annunciator
or tripping
device
RL 1
RL 2
RL 2
RL 1
PL 2
PL 2
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3
2
2
Alarm off when contacts closed
RL 3
PL 3
1
1
1
4
3
2
 
 
Case B - Relays normally energised, de-energise two to trip 
(Relays shown in de-energised state) 
1
4
3
2
5
8
7
6
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
1
4
3
2
5
8
7
6
To alarm
annunciator
or tripping
device
RL 1
RL 2
RL 2
RL 1
PL 2
PL 2
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3
2
2
Alarm off when contacts open
RL 3
PL 3
1
1
1
4
3
2