Fisher 244EH User Manual

Page of 64
3-9
Transmitter Behavior with Intermittent Sensor Detect ON
When the Intermittent Sensor Detect feature is switched 
ON
, the 
transmitter can eliminate the output pulse caused by intermittent open 
sensor conditions. Process temperature changes (
T) within 2% of the 
output range will be tracked normally by the transmitter’s output. A 
greater than 2% of the output range will activate the intermittent 
sensor algorithm. True open sensor conditions will cause the 
transmitter to go into alarm. 
Transmitter Behavior with Intermittent Sensor Detect OFF
When the Intermittent Sensor Detect feature is switched 
OFF
, the 
transmitter tracks all process temperature changes, even if they are the 
consequence of an intermittent sensor. The output delay due to the 
intermittent sensor algorithm will be eliminated. 
Implementation
The Intermittent Sensor Detect feature can be turned 
ON
 or 
OFF
 using 
a Model 244E transmitter with software version 5.4.1 or earlier with 
the Model 244EC software configuration tool when the transmitter is 
connected to the Model 244EC Configurator. 
Turning the Intermittent Sensor Detect feature 
OFF
 does not affect the 
time needed for the transmitter to output the correct alarm signal after 
detecting a true open sensor condition. However, the transmitter may 
briefly output a false temperature reading for less than 0.5 seconds in 
either direction (see Figure 3-4) up to100% of output range.
Figure 3-4. Open Sensor Response
(Three Cases)
Unless rapid response rate is necessary, the suggested setting of the 
Intermittent Sensor Detect mechanism is 
ON
0
0
5
10
15
20
25
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
T
ransmi
tt
er
Outpu
t
(m
A
)
Time (seconds)
A false temperature output in
either direction up to the
threshold value (100 % of output
range if Intermittent Sensor Detect
is OFF) is possible when an open
sensor condition is detected.
Normal open sensor responses
High Alarm
644-644_03