2-3
MOUNTING
The Model 244EH installs in a connection head or universal head 
mounted directly on a sensor assembly, apart from a sensor assembly 
using a universal head, or to a DIN rail using an optional mounting 
clip. The Model 244ER mounts directly to a wall or to a DIN rail.
The Models 244EH and 244ER transmitters will operate within 
specifications for ambient temperatures between –40 and 185 °F
(–40 and 85 °C).
In a direct mounting configuration using a Model 244EH transmitter, 
process heat is transferred from the thermowell to the transmitter via 
the connection head. If the expected connection head temperature is 
near or beyond specification limits, consider the use of additional 
thermowell lagging, an extension nipple, or a remote mounting 
configuration to isolate the transmitter from excessive temperatures. 
Figure 2-2 provides an example of the relationship between transmitter 
housing temperature rise and extension length. Use Figure 2-2 as a 
guide for determining adequate thermowell extension length.
Figure 2-2. Model 244EH Connection
Head Temperature Rise vs. Extension
Length
Example
The transmitter specification limit is 85 °C. If the ambient temperature 
is 55 °C and the process temperature to be measured is 800 °C, the 
maximum permissible connection head temperature rise is the 
transmitter specification limit minus the ambient temperature
(85 –55 °C), or 30 °C. In this case, an extension of 100 mm meets this 
requirement, but 125 mm provides a margin of 8 °C, thereby reducing 
any temperature effects in the transmitter.
304
4-
012
3A
 
60
50
40
30
20
10
0
75
100
125
150
175
200
225
T
e
m
p
erat
u
re
R
is
e
A
bo
ve
Ambien
t
(°C)
Extension Length (mm)
81
5
°C
Proc
ess
Temp
eratu
re
5
4
0
°C
Pr
oce
ss
Temperatu
re
250 °C
Process Temperature