Fisher 244ER User Manual

Page of 64
Rosemount Models 244EH and 244ER PC-Programmable Temperature Transmitters
3-8
Figure 4-1 illustrates an example of intermittent sensor detect with 
damping enabled. If the temperature undergoes a step change greater 
than the threshold value, or from 100 degrees to 110 degrees, and the 
damping is set to 5.0 seconds, the transmitter calculates a new reading 
every 500 ms using the damping equation, but holds the output at 
100 degrees for between 1.75 and 2.0 seconds. Within 1.75 and 
2.0 seconds, the transmitter outputs the reading that corresponds to 
the damping curve at that time (

), and continues to calculate and 
update the output reading every 500 ms thereafter (

) according to the 
damping equation. After 5 seconds, the transmitter outputs 
106.3 degrees, or 63% of the input change (

), and the output 
continues to approach the input curve according to the equation above.
NOTE
If the damping time constant is set between 0 and 2 seconds, the 
transmitter does not report the output change until the intermittent 
sensor algorithm validates the input signal. After validating the input 
signal, the transmitter outputs the value that corresponds to the 
damping curve at that time.
Figure 3-3. Damping Function when
Input Change is Greater Than the
Threshold Value
Intermittent Sensor Detect
(Advanced Feature)
NOTE
The Intermittent Sensor Detect feature is not available when using a 
Model 244EH with software revision 5.5.1. To determine the software 
version of a Model 244E temperature transmitter, first connect the 
transmitter to the Model 244EC configurator, open the Model 244EC 
software configuration tool, and then choose “service” from the Model 
244EC software menu.
The Intermittent Sensor Detect feature is designed to guard against 
process temperature readings caused by intermittent open sensor 
conditions (an intermittent sensor condition is an open sensor condition 
that lasts less than 0.7 seconds). By default, the transmitter is shipped 
with the Intermittent Sensor Detect feature switched 
ON
. In most 
applications, this is the preferred setting. The Intermittent Sensor 
Detect feature can be switched 
ON
 or 
OFF
 with the Model 244EC. The 
setting of this feature cannot be changed when using a Model 244E 
with version 5.5.1 software and a Model 244EC version 2.0 or earlier.
6
4
4
-64
4_0
2A