Amtrol fpt-1 Leaflet

Page of 2
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
IMPORTANT GENERAL SAFETY INFORMATION - 
ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
© 2014 AMTROL Inc. 
Part #: 9017-123 (01/14)
Mark of the
Originator
1400 Division Road, West Warwick, RI  USA 02893  
T: 800.426.8765    F: 800.293.1519
www.amtrol.com
Backflow preventer
with control valves
Fill cup or 
filling connection
Heated area
Drain
valve
Unheated area
Water
supply
FIRE-X-TROL
®
FPT-1 (C) through FPT-12 (C)
Backflow preventer
with control valves
Fill cup or 
filling connection
Heated area
Drain
valve
Unheated area
Water
supply
FIRE-X-TROL
®
FPT-20V (C)
through
FPT-210V (C)
EXPLOSION HAZARD. Failure to follow instruc-
tions in the accompanying product manual can 
cause rupture or explosion, possibly causing serious or fatal injury, leak-
ing or flooding and/or property damage.
Location of the FIRE-X-TROL
®
1.  The FIRE-X-TROL
 
should be installed on the water supply line to the 
unhea  ted area at a point between the backflow preventer and fill cup 
connection (Figure 1).
2. Once the FIRE-X-TROL is installed, check the system for any leakage. 
Make repairs if necessary.
Installation
THIS PRODUCT MUST BE INSTALLED BY A 
QUALIFIED PROFESSIONAL.
1.  Visually inspect FIRE-X-TROL for any damage.
2.  Hydraulic system pressure must be at zero.
3.  Attach nitrogen or dry air (-50°F/-46°C dew point or lower) supply to 
expansion chamber charging valve.
Pre-charge with nitrogen or dry air (-50°F/-46°C 
dew point or lower) only.
Do not use Oxygen - Explosion Hazard.
4.  Pre-charge to 2 psig (0.14 bar) below system static pressure at tank 
location.
Never pre-charge below 25% of the system 
maximum rated pressure.
5.  Remove charging hose. Carefully test charging valve for leakage.
6.  Replace plastic cap.
Protect against freezing temperatures.
Can cause damage and/or product failure.
Isolate expansion chamber during system 
hydro test.
Operating Istructions
1.  The FIRE-X-TROL is installed in the supply line between the backflow 
preventer and the fill cup connection. Its sealed-in air pre-charge 
chamber prevents water from entering it until the system pressure 
exceeds the pre-charge pressure. The FIRE-X-TROL is precharged 
to 25 psig (1.7 bar).
2.  As the water/antifreeze solution temperature rises, expanded system 
fluid enters the FIRE-X-TROL’s non-corrosive reservoir. The pre-
charge air chamber absorbs the pressure increase, keeping system 
pressure below maximum system rating.
3.  As the water/antifreeze temperature decreases, pressure in the air 
chamber forces system fluid back into the system.
4.  In antifreeze systems, this sequence allows the system antifreeze 
percentage to stay constant. Additional supply of water/antifreeze 
is not needed to replace fluid that would have escaped through a  
relief valve.
Maintenance
1.  Sprinkler system must be maintained and inspected per NFPA 25.
Warranty
Fire-X-Trol Models: One (1) Year Limited Warranty
Visit www.amtrol.com for complete warranty details.
Figure 1