Raypak 902B User Manual

Page of 60
10
In addition, the heater shall be installed such that the
gas  ignition  system  components  are  protected  from
water (dripping, spraying, rain, etc.) during appliance
operation  or  service  (circulator  replacement,  control
replacement, etc.).
Clearances
Indoor Installations
Heater
Side
Minimum Clearance
 from Combustible 
Surfaces
Recommended
Service 
Clearance
Floor*
0”
0”
Rear
1”
 6”
Water Side
12”
24”
Other Side
1”
24”
Top
1”
6”
Front
Open
24”
Vent
2”
2”
Table E: Clearances – Indoor Installations
TOP VIEW 
FRONT VIEW 
Venting not shown for clarity. Heater must be vented 
per instructions in this manual 
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor Installations
When installed according to the listed minimum clear-
ances  from  combustible  construction,  these  heaters
can  still  be  serviced  without  removing  permanent
structural construction around the heater. However, for
ease  of  servicing,  we  recommend  a  clearance  of  at
least  24  in.  in  front,  and  at  least  12  in.  on  the  water
connection side. This will allow the heater to be serv-
iced  in  its  installed  location  without  movement  or
removal of the heater.
Service  clearances  less  than  the  minimums  may
require removal of the heater to service either the heat
exchanger or the burner tray. In either case, the heater
must  be  installed  in  a  manner  that  will  enable  the
heater to be serviced without removing any structure
around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installa-
tion. Heaters must not be installed under an overhang
that is less than 3 ft from the top of the heater. Three
sides  must  be  open  in  the  area  under  the  overhang.
Roof  water  drainage  must  be  diverted  away  from
heaters installed under overhangs.
Heater
Side
Min. Clearance 
from Combustible
 Surfaces
Recommended
Service 
Clearance
Front
Open
24”
Rear
12”
24”
Water Side
36”
36”
Other Side
36”
36”
Top
Unobstructed
Unobstructed
Vent
N/A
N/A
Table F:  Clearances – Outdoor Installations
These  clearances  are  required  when  the  outdoor
vent cap is used. If installing the heater outdoors
with  a  vent  stack,  the  indoor  clearances  may  be
utilized.
The  combustion  air  intake  hood  MUST  be  used  for
outdoor  installations. The  hood  is  shipped  loose  and
installed on the side of the heater over the filter box at
the jobsite.
* DO NOT install on carpeting.