Zyliss CS9B-THO Leaflet

Page of 2
 
Temperature Range: Cool 66-90F (19-32C), Heat 60-80F (16-27C) 
 
Temporary Temperature Override feature: 45-minute default setting, adjustable in 5-minute increments  
 
Humidity control: Dehumidification only, Range 50-75%, Span is 5-10%. Requires special HVAC system with 
dehumidification circuit 
 
Pre-purge capability: Span 0-7200 seconds, default is 0 
 
CO2 control: Range 500-2000 ppm, Span 50-500 ppm 
 
Can optionally display space humidity, CO2, and outdoor temperature  
 
Dedicated ventilation output 
 
Outdoor sensor option, Bard PN 8403-061, can be used to: 
o  Limit minimum outdoor temperature for cooling operation 
o  Limit minimum outdoor temperature for heat pump operation (compressor lockout)  
o  Inhibit electric heat operation for heat pumps above selected outdoor temperature 
 
Remote indoor sensor option, Bard PN 8403-062, can be used to with following options: 
o  Use remote indoor sensor only  
o  Average remote indoor sensor and on-board sensor  
o  Highest of connected sensors 
o  Lowest of connected sensors 
 
Vertical mount, mounts to standard 2x4 handy-box installed vertically or horizontally 
 
Off-white 
 
 
 
 
Controller Connections:  Terminal legend 
          Terminal 
 
      Function   
    
 
 
           Type   
Form 
Dehumidification 
Output 
24VAC        SPST RELAY 
SC 
24VAC to Relay Outputs D, A, W2 
Power 
 
Ventilation Call 
Output 
24VAC        SPST RELAY 
W2 
2
nd
 Stage Heating 
Output 
24VAC        SPST RELAY 
W1/E 
1
st
 Stage Heating/Emer. Heat 
Output 
24VAC        SPST RELAY 
SC 
24VAC to Relay Outputs W1/E, Y2, Y1 
Power 
 
Y2 
2
nd
 Stage Compressor 
Output 
24VAC        SPST RELAY 
Y1 
1
st
 Stage Compressor 
Output 
24VAC        SPST RELAY 
Y0 
Economizer  
Output 
24VAC        SPST RELAY 
SC 
24VAC to Relay Outputs YO, O/B, G 
Power 
 
O/B 
Reversing Valve 
Output 
24VAC        SPST RELAY 
Indoor Blower 
Output 
24VAC        SPST RELAY 
IN9 
Not Used 
 
 
ROS 
Remote Occupancy Sensor 
Input 
Dry Contact (Input to GND) 
GND 
 
 
 
REM 
Remote Temperature Sensor 
Input 
10K Type II Thermistor 
+B 
Communications 
 
 
-A 
Communications 
 
 
OAT 
Outdoor Air Temperature Sensor 
Input 
10K Type II Thermistor 
LAS 
Leaving Air Temperature Sensor 
Input 
10K Type II Thermistor 
GND 
Control Ground 
 
 
Lockout Alarm 
Input 
Dry Contact (Input to GND) 
Com 
24VAC Common 
Power 
 
24V 
24VAC Hot 
Power 
 
 
 
 
Bard Manufacturing Company, Inc. 
Bryan, Ohio 43506 
www.bardhvac.com 
Form No. 
F1943 
May, 2012 
 
Supersedes:  F1943-212 
Due to our continuous product improvement policy, all 
specifications subject to change without notice. 
 
Before purchasing this appliance, read important energy cost 
and efficiency information available from your retailer. 
Page 