Alarm and fault messages 
4.2 Alarm and fault messages  
35 
Table 4-13 Fault 43 
 (Alarm) Vce monitor has responded 
Condition 
The CU has detected an inadmissible circuit voltage 
(voltage on semiconductor module between emitter and 
collector). 
Power unit is defective (various components could be 
the source of the problem) 
Transformer is defective 
Causes 
AC capacitors are incorrectly connected (connection 
does not comply with circuit diagram) 
Repair or replace the power unit 
Replace the transformer 
 
Measures 
Connect up the AC capacitors correctly 
 
Table 4-14 Fault 48 
(Alarm) Regeneration to the DC link 
Condition 
The CU has detected current flowing to the PV field 
(from AC to DC) which is higher than the set permissible 
current value. 
Parameter setting error (CU software) 
Causes 
Drive is defective 
Adjust the parameter setting 
 
Measures 
Repair the drive 
 
Table 4-15 Fault 62 
(Alarm) No checkback signal "Inverter ON" 
Condition 
The S7 is not receiving a checkback signal in response 
to the ON command to the drive 
CU defective 
Defective power unit 
Causes 
Profibus error 
Replace the defective components 
 
Measures 
Set up a Profibus connection