Overview
In combination with the safety-related automation systems of the 
SIMATIC PCS 7 process control system, the safety-related elec-
tronics modules of SIMATIC ET 200pro can be used to imple-
ment safety applications. The safety-related digital inputs record 
the signal statuses from safety-related sensors, and generate 
corresponding safety telegrams for the automation system. De-
pending on the safety telegrams of the automation system, the 
safety-related digital outputs trigger safe shut-down procedures. 
They are also responsible for monitoring short-circuits and 
cross-circuits up to the actuator. The safe communication with 
the automation systems is carried out over PROFIBUS with 
PROFIsafe.
All modules are certified up to SIL 3 (IEC 61508) and Cat. 4 
(EN954-1).
The following modules are available:
Safety-related digital input module EM 8/16 F-DI PROFIsafe
• 16 inputs (SIL2/Cat.3) or 8 inputs (SIL3/Cat.3 or Cat.4) 
• Suitable for standard switches and 3/4-wire proximity switches 
(BEROs)
• Rated input voltage 24 V DC 
• 4 short-circuit-proof sensor supplies for 4 inputs each 
• External sensor power supply possible 
• Group fault display (SF; red LED) 
• Fault display for each sensor power supply (Vs1F to Vs4F) is 
output on the VsF LED and the associated channels 
• Status and fault displays per input (dual-color green/red LED) 
• Identification data 
• Parameterizable diagnostics 
• Can only be operated in safety mode 
Safety-related digital input/output module EM 4/8 F-DI, 
4 F-DO 2 A
• Inputs 
- 8 inputs (SIL 2/Cat. 3) or 4 inputs (SIL 3/Cat. 3 or Cat. 4) 
- Suitable for standard switches and 3/4-wire proximity 
switches (BEROs) 
- Rated input voltage 24 V DC
- 2 short-circuit-proof sensor supplies for 4 inputs each 
- External sensor power supply possible 
• Outputs 
- 4 outputs, current sourcing/sinking 
- Output current 2 A 
- Rated load voltage 24 V DC 
- Suitable for solenoid valves, DC contactors and indicator 
lights
• Group fault display (SF; red LED) 
• Fault display for each sensor power supply (Vs1F to Vs2F) is 
output on the VsF LED and the associated channels 
• Status and fault displays per input/output (dual-color 
green/red LED) 
• Identification data 
• Parameterizable diagnostics 
• Achievable safety class SIL 3 
• Can only be operated in safety mode 
Technical specifications
For detailed technical specifications of the safety-related elec-
tronics modules, see: 
• Catalog IK PI
• Mall/CA 01 under "Distributed I/Os / ET 200pro"
© Siemens AG 2007