Determining Wire and Fuse Sizes 
The maximum motor currents in your application determines the recommended wore size. 
The following table gives the wire size in AWG. The “Power Lines” column applies to the 
inverter input power, output wires to the motor, the earth ground connection, and any other 
components shown in the “Basic System Description” on page 9. The “Signal Lines” 
column applies to any wire connecting to the two green connectors just inside the front 
cover panel. 
 
Motor Output 
Wiring 
Applicable 
equipment 
kW 
HP 
VT  CT  VT  CT 
Inverter Model 
Power Lines 
Signal Lines
Fuse (UL-rated, 
class J, 600V , 
Maximum 
allowable current) 
0.2 0.1  ¼  1/8 
WJ200-001SF 
0.4 0.2  ½  ¼ 
WJ200-002SF 
0.55  0.4 ¾  ½ 
WJ200-004SF 
AWG16 / 1.3mm
(75
°C only) 
10A 
1.1  0.75  1.5 1 
WJ200-007SF 
AWG12 / 3.3mm
(75
°C only) 
20A 
2.2 1.5  3  2 
WJ200-015SF 
3.0 2.2  4  3 
WJ200-022SF 
AWG10 / 5.3mm
2
 30A 
0.2 0.1  ¼  1/8 
WJ200-001LF 
0.4 0.2  ½  ¼ 
WJ200-002LF 
0.75  0.4 1  ½ 
WJ200-004LF 
10A 
1.1  0.75  1.5 1 
WJ200-007LF 
AWG16 / 1.3mm
2
 
2.2 1.5  3  2 
WJ200-015LF 
AWG14 / 2.1mm
(75
°C only) 
15A 
3.0 2.2  4  3 
WJ200-022LF 
AWG12 / 3.3mm
(75
°C only) 
20A 
5.5 3.7 7.5  5 
WJ200-037LF 
AWG10 / 5.3mm
(75
°C only) 
30A 
7.5 5.5  10  7.5 
WJ200-055LF 
11 7.5 15  10 
WJ200-075LF 
AWG6 / 13mm
(75
°C only) 
60A 
15 11 20  15 
WJ200-110LF 
AWG4 / 21mm
(75
°C only) 
80A 
18.5  15 25 20 
WJ200-150LF 
AWG2 / 34mm
(75
°C only) 
80A 
0.75  0.4 1  ½ 
WJ200-004HF 
1.5  0.75  2 1 
WJ200-007HF 
2.2 1.5  3  2 
WJ200-015HF 
AWG16 / 1.3mm
2
 
3.0 2.2  4  3 
WJ200-022HF 
10A 
4.0 3.0  5  4 
WJ200-030HF 
AWG14 / 2.1mm
2
 
5.5 4.0 7.5  5 
WJ200-040HF 
AWG12 / 3.3mm
2
 
(75
°C only) 
15A 
7.5 5.5  10  7.5 
WJ200-055HF 
11 7.5 15  10 
WJ200-075HF 
AWG10/ 5.3mm
2
 
(75
°C only) 
30A 
15 11 20  15 
WJ200-110HF 
AWG6 / 13mm
2
 
(75
°C only) 
50A 
18.5  15 25 20 
WJ200-150HF 
AWG6 / 13mm
2
 
(75
°C only) 
18 to 28 
AWG / 0.14 
to 0.75 mm
2
 
shielded wire
(see Note 4)
50A 
Note 1:  Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal 
connector sized for the wire gauge involved. Connector must be fixed by using 
the crimping tool specified by the connector manufacturer. 
Note 2:   Be sure to consider the capacity of the circuit breaker to be used. 
Note 3:   Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m). 
Note 4:   Use 18 AWG / 0.75mm
2
 wire for the alarm signal wire ([AL0], [AL1], [AL2] 
terminals).