Xantrex Technology 10 User Manual

Page of 68
Installation
2–12
975-0251-01-01
AC Wiring
Use a screwdriver to remove the screws which secure the AC wiring compartment 
cover plate. 
Inside you will see the compartment is divided into two sections, one labeled AC 
INPUT, the other labeled AC OUTPUT. Each side contains three pigtails: brown, 
blue and green/yellow. Wire nut connectors are provided.
Two AC wiring knockouts are provided on the AC compartment cover plate. After 
removing the knockouts, you can add strain reliefs for additional stability or 
conduit fittings if the wiring will be routed through conduit. Flexible conduit is 
recommended.
You must use 2.5 mm
2
 ES copper wire with insulation rated for 60 degrees 
centigrade or higher for both the AC input and AC output.
Figure 2-6 AC Compartment Cover Plate Screws
Remove these screws
Wire Nut Connectors
Wire Color
Description
Brown
Hot or Line
Blue
Neutral
Green/Yellow
Ground
Solid Green (AC output only)
Internal output neutral to ground bonding conductor
Important:
At the AC output, the green/yellow and solid green wires are already 
connected together.