Remote Control Panel
975-0251-01-01
3–5
Equalize or Three-Stage Charging (Switch #1)
Cycling this switch 
ON
 for 1 
second, then 
OFF
, will initiate an equalizing charge cycle. The battery charger 
must be engaged before cycling the switch. The switch must always be left in the 
OFF
 position. If it is left 
ON
, an equalizing charge cycle will initiate every time the 
charger is engaged - this could cause battery damage. The equalizing cycle is 
timed to last 8 hours from the time the switch is cycled, at which point the charger 
resumes normal charging in the float stage. The BATTERY LED blinks when 
equalizing. Refer to page 3–14 for a discussion of the theory and procedure for 
battery equalizing.
Battery Type (Switch #2 and 3)
Gel cell and wet cell batteries have slightly 
different charge voltage requirements and optimum battery charging is 
temperature dependent. For these reasons, the DIP switches allow four different 
battery charger voltage set points, depending on battery type and ambient 
temperature:
See page 3–16 for the specific voltages for each setting.
Auto Charge (Switch #4)
With the switch in the 
OFF
 position, the remote panel 
ON
/
OFF
 switch only controls the inverter operation. With the switch turned 
ON
, this 
switch allows the power 
ON
/
OFF
 switch on the front of the remote to control the 
battery charger as well as the inverter.
Figure 3-4 Freedom Remote Control Dip Switches
Battery Type and 
Temperature
Switch Position
Switch 2
Switch 3
Cool Wet Cell (< 27 °C)
Off
Off
Warm Wet Cell (> 27 °C) On
Off
Cool Gel Cell (< 27 °C)
Off
On
Warm Gel Cell (> 27 °C)
On
On