Freedom SW 230V Installation Guide
Planning Preparations
For dual input, the wire may be red or black; consult the 
documentation provided with the AC source (utility or generator).
Size of AC Output Wiring
Wire size must be coordinated with 
the current the wiring will carry. This current may be determined by 
the 15-amp (Freedom SW 3524-230) and 11-amp (Freedom SW 
2524-230) maximum inverter current, or by the bypass current, 
which is determined by the overcurrent protection provided ahead 
of the Freedom SW 230V.
Size of Wiring Downstream of the AC Output Breaker
The 
wiring used between the AC output breaker and your loads must be 
sized in accordance with the rating of the output breaker. 
Table 1 AC Wire Size In and Out of the Inverter/Chargers
MODELS
Freedom SW 230V
Breaker Size Used
30 amps
Wire Size
4 mm
2
 (minimum)
Color Coding
L: brown, black, or grey
N: blue
G: green with yellow stripe