50
Freedom SW 230V Installation Guide
Stacking Features
Example 4:
System composed of two stacked Freedom SW 3524-
230s. Each Freedom SW 3524-230 has a maximum charge capacity of 
90A. The two stacked Freedom SW 3524-230 inverter/chargers 
connected to the same battery bank can possibly produce a total of 
180A. 
The industry’s commonly accepted practice suggests a typical 
Flooded battery bank capacity (C) of 600Ah should not be charged 
beyond 25% of its capacity (150A). Therefore, when configuring 
the two stacked Freedom SW chargers, each charger may have a 
maximum charger output current of 75A (that is, 600 × 25% × 
1
/
2
into the common battery bank as described in the Calculations 
section. Also, the System Total BULK output current is calculated 
as 150A (that is, 75A + 75A).
To set the Max Chg Rate (%) setting in each Freedom SW 3524-230:
1.
Divide the maximum allowable charger output current of 75A 
by the Freedom SW 3524-230’s maximum charge capacity of 
90A.
So, 75 ÷ 90, gets an approximate value of 0.83 (or 83%) which 
can be set exactly to 83%.
2.
Set the Max Chg Rate (%) setting to 83 which means 83%.
In this example, the actual output current is limited to 83% of 90A 
which is 74A. Therefore, the actual System Total BULK output 
current
 comes out to just under 150A.