Overview
The timers screen allows the operator to view and adjust 
timer settings associated with compressor operation. 
There are different types of timers that the operator 
should be aware of listed below, see Figure 8-1. Timers 
Screen.
Changeover: 
•  The changeover timers will change from one type 
control to another once the compressor has started 
and then the timer has expired.
Bypass:
•   The bypass timers prevent certain alarm and trip 
checks from occurring until the compressor has 
started and then the time has expired.
Delays: 
•  Delays require the condition to occur for the specifi ed 
amount of time.
Timers: 
•  A general timer requiring the time to expire before 
the listed event can occur.
Timer Setpoints
Capacity Increase Start Delay:
•  At compressor startup, the capacity slide position is 
held at minimum position for this time period. This is 
to allow compressor and system conditions to stabi-
lize. After the timer expires, the slide is free to move 
in accordance to the system demands.
Minimum Compressor Pre-lube Time:
•  This is the length of time the oil pump will run, after 
establishing Pre-lube Oil Pressure, to prime the oil cir-
cuit before starting the compressor.
Figure 8-1. Timers Screen
Section 8 • Timers