Emerson 20/20 User Manual

Page of 120
12 – 1
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Section 12 • Service Options
Overview
The Service Option screen allows the operator the abil-
ity to force individual digital or analog outputs ON. This 
feature is used for diagnostic purposes during initial 
setup and/or if the operator suspects an issue with the 
outputs. The buttons in this screen are not available 
while the compressor is running, see Figure 12-1 Service 
Options Screen. 
Digital Outputs
The digital output buttons are momentary toggle but-
tons. The output will be active while the operator has his 
fi nger on the button. The output will deactivate when 
the operators fi nger is removed. The operator can mea-
sure the output at the terminal block or view the output 
by watching the LEDs located on the cards.
Compressor Start:
•  Activates the output assigned to the compressor mo-
tor starter. The output is connected to terminal 11 
and is the 1st LED on card 1.
Oil Pump Start:
•  Activates the output assigned to the oil pump. The 
output is connected to terminal 12 and is the 2nd 
LED down on card 1.
Capacity Increase Motor:
•  Activates the output assigned to the increase input 
of the capacity actuator. The output is connected to 
terminal 13 and is the 3rd LED down on card 1.
Capacity Decrease Motor:
•  Activates the output assigned to the decrease input 
of the capacity actuator. The output is connected to 
terminal 14 and is the 4th LED down on card 1.
Volume Increase Motor:
•  Activates the output assigned to the increase input 
Figure 12-1. Service Options Screen