Emerson AE4-1395 User Manual

Page of 19
5
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE4-1395
Application Engineering
B
U
L
L
E
T
I
N
Compressor operation during the loaded state should 
always be inside of the envelope. The envelopes 
represent allowable operation of the compressor with 
20F° suction superheat at rated voltage. If the specified
modulation ranges are exceeded, overheating of the 
compressor and tripping of the overload can occur 
because of inadequate motor cooling. 
Solenoid Valve and Coil
The  external  solenoid  valve  and  coil  specified  by
Emerson must be used since this is a critical component 
for the proper functioning of this compressor. The 
solenoid valve and coil are designed for approximately 
32 million cycles. Do not attempt to substitute 
replacement coils or valves; use only the replacement 
parts  specified  in
Table 4.  Refer to the Service 
Procedures section for information on changing the 
modulation valves.
Pressure Fluctuations
During scroll modulation the suction and the discharge 
pressure  will  fluctuate.  This  fluctuation  should  be
observed during unit testing. The installation and setting 
of pressure controls should take this into account. 
During the unloaded state, the discharge pressure will 
decrease and the suction pressure will increase. This 
normal  pressure  fluctuation  has  had  no  observable
effect on the reliability of system components, however, 
component manufacturers should be consulted to 
ensure the proper application of their products.
Piping
Unlike a variable speed compressor whose mass flow
and gas velocity changes with its speed, the digital 
scroll’s pumping capacity is equal to its 100% capacity 
while it is pumping. For this reason the gas velocity 
remains high even during periods when the capacity 
demand is low. Because the mass flow and gas velocity
remain high, piping may be designed as if it were 
designed for a non capacity controlled compressor. For 
vertical piping a trap every 20 feet should be sufficient
to ensure proper oil return. This recommendation is 
based upon a minimum 1500 fpm velocity or higher. 
When the digital scroll compressor is part of a tandem, 
a double riser should be considered to assure that the 
velocity remains above 1500 fpm when only the digital 
scroll is running. 
Start Up and Shut Down
To improve the starting characteristics of the digital 
scroll compressor, the the Emerson controllers delay 
loading the compressor for 0.1 seconds. Likewise, to 
eliminate the reverse rotation sound at shut down the 
compressor is unloaded 0.5 seconds before shut down.
Compressor Cycling
Because of the digital scroll's seamless capacity 
modulation from 10% to 100%, capacity short cycling 
should not be a problem for single compressors. 
However, if the digital compressor is in tandem with a 
non modulated scroll, short cycling of the non modulated 
compressor may be a problem if the system control is 
not designed and set correctly. The Emerson digital 
controllers have a built in two minute anti-short cycle 
timer to prevent short cycling.
Sound Characteristics 
The sound spectrum of the loaded state and the 
unloaded state are different. 
Special consideration 
should be given to the transition sound between the 
loaded and unloaded states. If the transition sound 
is unacceptable, a heavy sound blanket should 
be applied to the compressor. Fabricating Services 
(www.fabsrv.com) is a one source for scroll compressor 
sound blankets.
The Emerson controllers unload the compressor a 
fraction of a second before shut down allowing the scroll 
set to unload, ensuring a relatively quiet shutdown.
Internal Pressure Relief (IPR) Valve 
WARNING
A high pressure control must be used in all 
ZRD94-125KC and ZPD103-182KC applications 
because these compressors do not have internal 
pressure relief (IPR) valves.
High Pressure Control 
As mentioned above, not all digital scrolls have IPR 
valves, therefore high pressure controls are required 
in some applications. The recommended maximum cut 
out setting is 425 psig (30 bar) for R-407C & R-22 and 
650 psig (45 bar) for R-410A. The high pressure control 
should have a manual reset feature for the highest 
level of system protection. This pressure control must 
act independently of the digital compressor controller.
Low Pressure Control
Air-conditioning units can be protected against high 
discharge temperatures through a low pressure control in 
the suction line. Testing has shown that a cut out setting 
of not lower than 55 psig (3.8 bar) for R-410A and 25 
psig (1.7 bar) for R-407C & R-22 will adequately protect 
the compressor against overheating from loss of charge, 
blower failure in a TXV system, etc. A higher level of 
protection is achieved if the low pressure control is set to 
cut out at 95 psig (6.7 bar) for R-410A and 55 psig (3.8