6-56
Computer Group Literature Center Web Site
Subassembly Reference
6
Figure 6-11. Dual Breaker DC Power Distribution Panel—Front View
The dual breaker DC power distribution panel is available without the two 
30A circuit breakers, provided that circuit breaker protection is provided 
elsewhere and there is allowance for a rating of 30A for each feed.
Use either a standard Smart cable or the optional right-angle Smart cable 
(for limited space requirements) to connect the DC power source to the 
system. Cable length is 10 feet.
H.110 DC Power Distribution Panel (CPX8216T)
The H.110 DC power distribution panel provides dual DC input for system 
power as well six additional power input connectors for the H.110 BAT 
and Ring Voltages. The H.110 DC power distribution panel is only 
compatible with the CPX8216T system.
!
Caution
Caution
The six H.110 power inputs must only be attached to approved Telephone 
Network Voltage (TNV) branch circuits. TNV branch circuits must 
comply with all requirements called for in these safety standards: IEC 
950/EN60 950, UL #1950, and CSA #950. Attaching those inputs to non-
TNV-approved power sources will cause the system to fail compliance 
with safety regulations and may cause damage to the system backplane and 
system components.
Part Number
Cable Description
30-W2750E01A
Standard Smart cable 
30-W2750E03A
Right-angle Smart cable