Installation Addendum
For ET 355 Monitor HL
Read and understand all safety information before installing and using this product.
3M Touch Systems Proprietary Information
1
About this addendum
This document supplements information in the ET 350 
Monitor User’s Installation Guide
 with details that pertain 
to the 3M Dynapro
TM
 ET 355 Monitor HL.
Translations of intended use and 
product safety information
Translations of intended use and product safety 
information are at the end of this document (starting on 
page 8). Definitions of safety symbols that are used on the  
ET 355 Monitor HL are on page 4 in English and other 
languages.
Intended Use
The ET 355 Monitor HL (hereafter, ET 355 monitor) is 
intended to provide touch screen functions for industrial 
applications in hazardous locations when the monitor is 
connected to a host computer.
The ET 355 monitor is suitable for use in non-hazardous 
locations
 and also in the following types of hazardous 
locations
. Using the monitor in locations other than these 
will invalidate the warranty and will be solely the user’s 
risk and responsibility:
Class I, Division 2, Groups A, B, C, and D hazardous locations; 
temperature code T6 (less than or equal to 85°C).
 Where:
volatile flammable liquids or flammable gases or vapors 
exist, but are normally confined within closed containers;
ignitable concentrations of gases, vapors or liquids are 
normally prevented by positive mechanical ventilation;
adjacent to a Class I, Division 1 location, where ignitable 
concentrations might be occasionally communicated.
Class II, Division 2, Groups F and G hazardous locations; 
temperature code T6 (less than or equal to 85°C)
. Where:
combustible dust is not normally in the air in ignitable 
concentrations;
dust accumulations are normally insufficient to interfere 
with normal operation of electrical equipment;
dust may be in suspension in the air as the result of 
infrequent malfunctioning of equipment; or
dust accumulation may be sufficient to interfere with safe 
dissipation of heat or may be ignitable by abnormal 
operation.
Wiring methods must be in accordance with Class I, 
Division 2 wiring methods, Article 501-4(b) of the 
National Electric Code, NFPA 70 for installations in the 
U.S., or as specified in Section 18-1J2 of the Canadian 
Electrical Code for installations within Canada and in 
accordance with the authority having jurisdiction.
Accessory connections must be evaluated in the end 
application (i.e. nonincendive circuits).
Important
If there appears to be a conflict between information in the ET 
350 Monitor User’s Installation Guide
 and this Installation 
Addendum: ET 355 Industrial Monitor HL
 (for hazardous 
locations), this addendum takes precedence.
If there appears to be a conflict between information in this 
addendum and the Installation Addendum for the ET 350 Monitor 
with Heater and ET 355 Monitor HL with Heater
, the latter takes 
precedence.
Important
For more detailed definitions of hazardous locations, refer to the 
UL web site <http://www.ul.com>.
Important
The ET 355 monitor HL is a component. After the monitor is 
installed in a hazardous location for which it is certified, the whole 
system or end product of which it is a part must be inspected to 
confirm seal ratings and compliance with all electrical codes. If 
your ET  355 monitor HL comes with the KVM extender option, it 
is not necessary to have the KVM local unit evaluated since the 
local unit is not to be situated in a hazardous location.